5.5 Local Display

5.5.1 Procedure to Set the Integral Indicator

F0505.ai

Corresponding

decimal point

Engineering Unit
Eng. Unit @ 1/10
Eng. Unit @ 1/100
Eng. Unit @ 1/1000

LCD value

(kPa)

Exponent

2

23.46

2

2.35

2

0.23

2

0.02

Select from Parameter Displays (1-4)

(Display Selection)

Select items to be displayed in the lower text field

(Information Selection)

Specify whether DISPLAY1, DISPLAY2, DISPLAY3, or

DISPLAY4 should be displayed.

Specify whether tag, parameter, unit, or status should be

displayed.

Select parameters to be displayed.

Written as by 6 characters or 6 characters plus “/”,“.”.(*1)

Written as by 6 characters or 6 characters plus “/”,“.”.(*1)

Specify parameters to be displayed

(Parameter Selection)

Perform ON/OFF setting of the bar graph

(Bar Graph)

Set the display period

(Display Cycle)

Time unit: 400ms; When the value set is “7”, the same
display continues for about 2.8 seconds.

Example display of exponent setting:
The LCD value for exponent setting when the actual
pressure value is 23.4568 kPa and the decimal point
selected is 2.

Set an exponent

(Exponent Mode)

Set the display contents for the block tag to be displayed in

the lower text field

(Display Tag)

Set the display contents

of the unit

(Display unit)

Select whether the unit to be displayed in the lower text field

should be set to automatic or on a customized basis

(Unit Selection)

CUSTOM is

selected

AUTO is

selected

*1:

Combination of up to 6 characters of alphanumeric and the symbols of [/], [.] and [ ] (space) are available.

If the other characters are specified, space will be displayed.

The symbols of [/] and [.] cannot be specified on the head of a string.

Figure 5.3

Procedures to Set the Built-in Display