<6. Explanation of Basic Items>

6-1

IM 01C25T04-01EN

6. Explanation of Basic Items

6.1 Outline

This chapter describes brief explanation of the

SENSOR transducer block, the LCD transducer

block, the AI function block, and the Totalizer

function block.

Actual mode
Many parameters require a change of the mode

of the function block to O/S (Out of Service) when

their data is changed. To change the mode of the

function block, its Target Mode (TARGET_MODE)

needs to be changed. The Actual Mode (MODE_

BLK) is comprised of the three sub-parameters

below:
(1) Actual (Actual mode):

Indicates the current operating condition.

(2) Permit (Permitted mode):

Indicates the operating condition that the block

is allowed to take.

(3) Normal (Normal mode):

Indicates the operating condition that the block

will usually take.

6.2 SENSOR Transducer Block

The SENSOR transducer block is in between the

sensor and the AI function blocks. It calculates

pressure/differential pressure, static pressure,

and capsule temperature from sensor signals.

Then it performs damping and range checks for

the measured values of these three variables and

sends signals to the AI function block.

6.2.1 Functional Block

Figure 6.1 presents the functional block of the

SENSOR transducer. The calculated values

of pressure/differential pressure, H-side static

pressure, L-side static pressure, and capsule

temperature are assigned to PRIMARY_VALUE,

STATIC_PRESSURE_HIGH_VALUE, STATIC_

PRESSURE_LOW_VALUE, TEMPERATURE_

VALUE and, AMP_TEMP_VAL respectively.

Measured values output to the AI function blocks or

Totalizer function block are selected by the Channel

parameter of those blocks.

Pressure

Raw Value

Pressure

Value

Scale

In

Scale

Out

Primary

Value

Calculate Value

Analog

Input 1

Analog

Input 2

Analog

Input 3

Totlizer

Static Pressure High Side Value

Static Pressure Low Side Value

Capsule Temperature

Amplifier Temperature

Pressure

Raw Value Unit

Pressure Value Unit

Primary Value Unit

Calculate Value Unit

Static Pressure Unit

Temperature Unit

Linear

User defined

(table)

Square root

Characterization

Type

Low Flow Cut Off

Simulation

Simulation

Value

Enable

Calculate

Coefficient

Channel

Sensor

signals

Disable

F0601.ai

Figure 6.1

SENSOR Transducer Functional Block