<6. Explanation of Basic Items>

6-2

IM 01C25T04-01EN

6.2.2 Target Mode

The Block modes permitted for the SENSOR

transducer block are Automatic (Auto) and Out of

Service (O/S). The mode must be set to Auto under

normal operating conditions, and to O/S when

making changes to an important parameter. For

parameters that can only be changed in the Auto

and O/S modes, refer to the parameter list for the

SENSOR Transducer block.

6.2.3 Basic Parameter of SENSOR

Transducer Block

Scale In (SCALE_IN)
Scale In is the input conversion of pressure using

high and low scale. The related unit is the pressure

unit. Refer to 5.1.2 for configurations.

Primary Value (PRIMARY_VALUE)
This parameter contains the measured value and

status available to the function block.

Calculate Coefficient (CALCULATE_COEF)
Coefficient for calculating Calculate Value

(CALCULATE_VALUE). Calculate Coefficient can

be considered as Kfactor for flow rate calculation.

Refer to Subsection 5.3.4 for Kfactor calculation.

Calculated Value (CALUCULATE_VALUE)
Calculation result of (Primary Value) × (Calculate

Coefficient)

Calculated Value Unit (CALCULATE_UNIT)
Unit for Calculate Value.

Characterization Type (LIN_TYPE)
Characterization type of output signal can be select

from Linear, user defind (table) or Square root. user

defind (table) is used to compensate the output for

non-linear applications. For the measured pressure,

a maximum of 31 coordinates can be specified

between 0 – 100%. Please refer 5.1.3 to for more

information.

Low Flow Cut Off (LOW_FLOW_CUTOFF)
This is the point in percent of flow until the output

of the flow function is set to Zero. It is used for

suppressing low flow values. Refer to 5.3.1 for

detail.

6.3 LCD Transducer Block

6.3.1 Outline of the Functions

The LCD transducer block controls alarms and

measured values that are displayed on the integral

indicator. It displays not only OUT signals from the

AI blocks, but also I/O signals of the Installed blocks

on the integral indicator.

6.3.2 Target Mode

The Target modes permitted for the LCD transducer

block are Automatic (Auto) and Out of Service (O/

S). Settings can be changed in the AUTO mode for

this block, except the Block tag parameter.

6.3.3 Display Contents of the Integral

Indicator

The components of the integral indicator are the bar

graph, the title field, the center field for numerical

values, the lower text field, and auxiliary characters.

The contents and meanings of these components

are as follows: