4 ai function block, 1 function blocks, Ai function block -6 6.4.1 – Yokogawa EJX115A User Manual

Page 39: Function blocks -6

Advertising
background image

<6. Explanation of Basic Items>

6-6

IM 01C25T04-01EN

6.4 AI Function Block

The AI function block is a unit of the software.

During execution, it incorporates data from the

SENSOR transducer block. After execution, it

updates analog outputs and processes newly

generated alarms. AI function blocks can provide

a discrete output which shows the status of LO,

LO_LO, HI, or HI_HI. In terms of function, there is

no difference between the three AI function blocks

provided in DPharp.

6.4.1 Function Blocks

The AI function block, via the Channel, incorporates

analog signals from the transducer block, performs

scaling processing, filtering, signal linearization,

fail safe control and alarm processing before

outputting. It has the function to generate a discrete

output. Figure 6.3 presents the AI function block.

Simulate

PV from TB

Scaling

PV_SCALE

Simulate.Enable

Linearization

LIN_TYPE

Scaling

OUT_SCALE

Filter

PV_FTIME

Limit Check

HI, HI_HI

LO, LO_LO

Fail

Safe

Value, Status

AUTO

MAN

OUT

OS

OUT

OUT

MODE_BLK. Actual

Value, Status

Value, Status

F0605.ai

Figure 6.3

Diagram of the AI Functional Block

Advertising