<6. Explanation of Basic Items>

6-7

IM 01C25T04-01EN

6.4.2 Target Mode

The Target modes permitted for the AI function

block are Automatic (Auto), Manual (Man), and

Out of Service (O/S). When the Target mode of PB

(Physical Block) is Out of Service (O/S), Actual is

Out of Service (O/S) even if Automatic (Auto) or

Manual (Man) is written to Target.

6.4.3 Basic Parameter of AI function block

Output Value (OUT)
The function block parameter OUT contains the

current measurement value in a vendor specific

or configuration adjusted engineering unit and the

belonging status in Auto Mode. Also contains the

value and status set by an operator in Man Mode.

Simulation (SIMULATE)
Simulation parameter is to simulation mainly for

checking arbitrarily set the value and input status

from SENSROR Transducer block.

PV Scale (PV_SCALE)
Conversion of the process variable into percent

using the high and low scale values.

Linearization type (LIN_TYPE)
Linearization type of output signal can be select

from Linear or Square root. Linearization type of

AI function block can apply to have different output

mode for display and output signal. (For example,

Display mode: Square root, Output mode: Linear)

Out Scale (OUT_SCALE)
Scale of the process variable. This parameter

contains the values of the lower limit and upper limit

effective range, the code number of the engineering

unit of process variable and the useful number of

digits on the right hand side of the decimal point.

Filter Time Const (PV_FTIME)
Damping time of the process variable.

Fail Safe Mode (FSAFE_TYPE)
Fail Safe Mode is parameter used to define the

reaction of the device, if a BAD status of signal to

AI function block (OUT.Status and OUT.Value) is

detected. This is available only when Target Mode

of AI function block is in “Auto”. Refer to 5.4.1 for

configuration.

Table 6.2

Fail Safe Mode (Classic Status)

Fail Safe Mode

Output Value and Status (Quality)

Default value is

used as output

value

value Fail Safe Default value
Status UNCERTAIN - Substitute Value

Storing last valid

output value

value Last stored valid OUT value
Status UNCERTAIN - Last Usable Value

The calculated

output value is

incorrect

value wrong calculated value
Status BAD - *(* as calculated)

Table 6.3

Fail Safe Mode (Condensed Status)

Fail Safe Mode

Output Value and Status (Quality)

Default value is

used as output

value

value Fail Safe Default value
Status BAD - Passivated, Constant *

1

UNCERTAIN - Substitute Set *

2

UNCERTAIN - Process Related *

3

UNCERTAIN - Substitute Set *

4

Storing last valid

output value

value Last stored valid OUT value
Status BAD - Passivated, Constant *

1

UNCERTAIN - Substitute Set *

2

UNCERTAIN - Process Related *

3

UNCERTAIN - Substitute Set *

4

The calculated

output value is

incorrect

value wrong calculated value
Status BAD - Passivated, Constant *

1

BAD - Maintenance Alarm *

2

BAD - Process Related *

3

BAD -Function Check *

4

*1:

When input status = BAD - Passivated

*2:

When input status = BAD - Maintenance Alarm

*3:

When input status = BAD - Process Related

*4:

When input status = BAD - Function Check

6.5 Totalizer Function Block

6.5.1 Functional Block

The Totalizer function block, incorporates

analog signal from SENSOR transducer block,

performs integrate a rate or another quantity to

the corresponding integral. And also, this function

block can be tailored for different applications or

determines the fail-safe behavior.

6.5.2 Target Mode

The Target Mode permitted for the Totalizer function

block are Automatic (Auto), Manual (Man), and Out

of Service (O/S).