<6. Explanation of Basic Items>

6-8

IM 01C25T04-01EN

6.5.3 Totalizer Value Set (SET_TOT)

Reset of the internal value of the function block

algorithm to 0 or set this value to which configured

in Preset Value (PRESET_VALUE). This parameter

affects the current totalized value immediately. This

function is level sensitive. While this is set to Reset

or Preset, the status of the totalized value shall be

UNCERTAIN-initial value. The parameter Totalized

Value (TOTAL) is affected if the block is in Auto

Mode.

Totalized

Value

SET_TOT

0.0

UNCERTAIN-init

value

PRESET_TOT

UNCERTAIN-init

value

Time

Time

F0606.ai

0.0

2
1
0

The following selections of this function block

parameter are possible.

0: Totalize: Normal operation of the Totalizer

1: Reset; Assign value 0 to Totalizer

2: Preset; Assign value of Present Value to

Totalizer

6.5.4 Mode (MODE_TOT)

This parameter governs the behavior of the

totalization. The following selections are possible:
Pos. and neg. values; True arithmetic integration of

the incoming rate values.
Positive values only; Totalization of positive

incoming rate values only.
Negative values only; Totalization of negative

incoming rate values only.
Hold Count; Totalization stopped.

6.5.5 Fail Safe Mode (FAIL_TOT)

Fail safe mode of the Totalizer function block. This

parameter governs the behavior of the function

block during the occurrence of input values with

BAD status. The following selections are possible.

Run; Totalization is continued using the input values

despite the BAD status. The status is ignored.
Hold; Totalization is stopped during occurrence of

BAD status of incoming values.
Memory; Totalization is continued based on the last

incoming value with GOOD status before the first

occurrence of BAD status.

Table 6.4

Fail Safe Mode (Classic Status)

FAIL_TOT mode

TOTAL Value and Status(Quality) *

1

Run

value Totalization is continued using the

input values

Status UNCERTAIN - Non Specific

Hold

value Totalization is stopped
Status UNCERTAIN - Last Usable Value

Memory

value Totalization is continued based on

the last incoming value with GOOD

status

Status UNCERTAIN - Non Specific

*1:

When SET_TOT=TOTALIZE & MODE_TOT<>HOLD,

input status <> out of serivce

Table 6.5

Fail Safe Mode (Condensed Status)

FAIL_TOT mode

TOTAL Value and Status(Quality) *

1

Run

value Totalization is continued using the

input values

Status BAD - *(* same as input)

Hold

value Totalization is stopped
Status BAD - *(* same as input)

Memory

value Totalization is continued based on

the last incoming value with GOOD

status

Status UNCERTAIN - Substitute set

*1:

When SET_TOT=TOTALIZE & MODE_TOT<>HOLD,

input status <> BAD - Passivated

Value, Status

AUTO

MAN

TOTAL

OS

TOTAL

TOTAL

MODE_BLK. Actual

PV from TB

(CHANNEL)

Fail safe

handling

FAIL_TOT

Totalize mode

handling

MODE_TOT

Totalize start /

reset /preset

handling

SET_TOT

Totalization

Limit Check

HI, HI_HI

LO, LO_LO

Value, Status

F0607.ai

Figure 6.4

Totalizer Function Block