<7. In-Process Operation>

7-1

IM 01C25T04-01EN

7. In-Process Operation

This chapter describes the procedure performed

when changing the operation of the function block

of the transmitter in process.

7.1 Mode Transition

When the function block mode is changed to Out_

Of_Service, the function block pauses.
When the function block mode is changed to

Manual, the function block suspends updating of

output values. In this case alone, it is possible to

write a value to the OUT parameter of the block for

output.

7.2 Generation of Alarm

7.2.1 Indication of Alarm

When the self-diagnostics function indicates that a

device is faulty, a diagnostic message (DIAGNOSIS

or DIAGNOSIS_EXTENSION) is issued from the

physical block. When a diagnostic message is

detected in each function block or a diagnostic

message in the process value (process alarm) is

detected, a diagnostic message is issued from

each block. If an LCD indicator is installed, the error

number is displayed as AL.XX.

If two or more alarms are issued, multiple error

numbers are displayed.
For details of ALARM, refer to Section 8.2.

F0701.ai

Figure 7.1

Error Identification on Indicator

7.2.2 Status of Each Parameter in Failure

Mode

Status has Classic Status and Condensed Status.
Classic Status is a conventional alarm and does

not support the NAMUR NE107. Condensed Status

is an alarm which was added to PA Profile 3.01 or

later and supports the NAMUR NE107.
The following standard categories of instrument

diagnostics are defined for the NAMUR NE-107.
F (Failed):

An alarm category that indicates a failure has

occurred in the instrument or in its peripheral

devices.

C (Check Function):

An alarm category that indicates that a detected

failure is a temporary event.

S (Off Specification):

An alarm category that indicates that the

detected failure was caused by the

instrument being used outside of its range

or because a discrepancy has occurred

between the set value and measured

value. The alarm was caused either by the

instrument or process state.

M (Maintenance):

An alarm category for a detected failure that

has a low level of urgency but is a failure

that could develop into a problem causing

restrictions in instrument functionality in

some environments.

Classic Status and Condensed Status can be

switched by using the Condensed Status/Diagnosis

(PB.COND_STATUS_DIAG) parameter.

• Procedure to call up the display

DTM

[Menu] → Device → Configulation →

Query Device → Query Device PB →

Condensed Status/Diagnosis

EDD

[Menu] → Device → Query Device →

Phsical Block → Index 33-51 →

Condensed Status/Diagnosis