1 sensor transducer block, 2 ai function blocks, 3 physical block – Yokogawa EJX115A User Manual

Page 44: Sensor transducer block -3, Ai function blocks -3, Physical block -3

Advertising
background image

<7. In-Process Operation>

7-3

IM 01C25T04-01EN

7.3.1 Sensor Transducer Block

It is necessary to set parameters as shown in

Table 7.2 when the simulation function is used.

When SIMULATE MODE in SENSOR Transducer

block described at Table 7.2 is set to “1: Pressure

Value”, the sensor transducer block uses the

simulation value instead of the pressure value

“SECONDARY_VALUE_1” before carrying out

scaling and linearization.

• Procedure to call up the display

DTM

Diag and Service → Sensor Transducer

Block →

EDD

[Menu] → Device → Simulation →

Sensor Transducer Block →

Simulation (Pressure) →

Table 7.2

Simulation parameters in the

transducer block

Index Parameters

Description

Valid

Range

Initial

Value

118

SIMULATE_

MODE

Select “1:

Pressure

Value” when

the simulation

function is used.

0:Off

1:Pressure

Value

0:Off

119

SIMULATE_

VALUE

Set the value

to be simulated

instead of

SECONDARY_

VALUE_1.

None

Value: 0

Status:

Bad

7.3.2 AI Function Blocks

When the parameters are set in the transducer

block, it is necessary to set parameters as shown in

Table 7.3 in the AI function blocks. When Simulate_

Enabled in AI function blocks described at Table 7.3

is set to “1: Enabled”, the each AI function block that

set this parameter uses the simulation value instead

of the data from the transducer block.

• Procedure to call up the display

DTM

Diag and Service → Analog Input (1-3)

EDD

[Menu] → Device → Simulation →

Function Block (1-3) - Analog Input →

Simulation (Measured Value) →

Table 7.3

Simulation parameters in the AI block

Sub-

Index Parameters

Description

Valid

Range

Initial

Value

1

Simulate_

Status

Set the data

status to be

simulated.

Unsigned8 0

2

Simulate_

Value

Set the value of

the data to be

simulated.

Float

0

3

Simulate_

Enabled

Controls the

simulation

function of this

block.

0:

Disabled,

1: Enabled

0:
Disabled

7.3.3 Physical Block

It is necessary to set alarm parameters as shown in

the Physical block when the simulation function is

used.

• Procedure to call up the display

DTM

Diag and Service → Physical Block →

EDD

[Menu] → Device → Simulation →

Physical Block →

Simulation (Diagnosis Extension) →

Table 7.4

Alarm parameters as simulation function in the physical block

Index

Parameters

Description

Valid Range

Initial Value

60

DIAGNOSIS_SIM_

MODE

When the hardware simulation jumper is on, DIAGNOSIS_SIM_

MODE is set to enable, and the bits are set to “on”, the alarms (or

warnings) can be modified.

0: Disabled,

1: Enabled

0: Disabled

61

DIAGNOSIS_SIM_

EXTENSION

Definition of supported DIAGNOSIS_EXTENSION information-

bits for testing alarms and warnings can be modified.

0: Off,

1: On

0x00, 0x00, 0x00,

0x00, 0x00, 0x00

Advertising