<7. In-Process Operation>

7-4

IM 01C25T04-01EN

7.4 Write lock (Write-protect)

function

The transmitter is provided with a write lock (write-

protect) function to restrict write operations to

blocks and prevent inadvertent writing of parameter

data. To enable this function, use the write lock

switch (Hard W Lock) or the WRITE_LOCKING

(Physical block index 34) (Soft W Lock).

The CPU assembly of the transmitter is provided

with a write lock switch (switch 2 in Figure 7.3).

Setting switch 2 to On activates the write lock

function.

When the write lock switch is disabled, set 0

(protected) for WRITE_LOCKING (index 34) of the

physical block to enable the write lock function.

• Procedure to call up the display

DTM

Physical Block → Configulation → Write

Locking →

EDD

[Menu] → Device → Write Locking →

→ On

Write lock enabled

→ Off

Write lock disabled

These parameters and issue shall control the

parameter access as defined in Table 7.5.

Table 7.5

Access protection

HARDWARE_WRITE_

PROTECTION

WRITE_LOCKING

Remote

access

possible

0 (unprotected)

2457 (unprotected)

YES

0 (protected)

NO

2 (protected, no manual

operation permitted)

NO

F0703.ai

Amplifier Assembly

SIMULATE_ENABLE switch

1

2

O

N

O

N

"ON" : Write lock enable

WRITE LOCK

Figure 7.3

Write lock Switch

7.5 Local Operation Interface

WARNING

The local operation switch on LCD must not

be used in the hazardous area. When it is

necessary to use the switch, operate it in a non-

hazardous location.

IMPORTANT

Do not turn off the power to the transmitter

immediately after performing parameter setting.

Powering off within 30 seconds of performing

this procedure will return the parameter to its

previous setting.

The zero point can be adjusted and the Ident

number and Bus address can be set by using

the push button below the LCD display and the

adjustment screw on the main body. Before the

setting, check the following items at the Local

Operation Interface.

• The Write Locking (WRITE_LOCKING)

parameter and the hardware write lock switch

are both turned off and disabled. For the

procedure, see Chapter 7.4. When the Write

Locking (WRITE_LOCKING) parameter is

enabled, the key mark appears on the LCD

display, which indicates that no settings can be

made except for zero point adjustment.

• The Local Operation (LOCAL_OP_ENA)

parameter is enabled.

• The TEST screen is disabled.

• Communication is set to aperiodic. Even during

periodic communication, zero point adjustment

is possible.

• The degree of adjustment depends on the

speed of turning the adjustment screw. Turn the

screw slowly for fine tuning and turn the screw

fast for quick tuning.

External Adjustment

screw cover

F0704.ai

Figure 7.4

External Adjustment Screw