<7. In-Process Operation>

7-5

IM 01C25T04-01EN

F0705.ai

Integral indicator

Local operation switch

(Push-button)

Note 1: Use a thin bar which has a

blunt tip, e.g., a hexagonal

wrench, to press the Local

operation switch.

Note 2: The switch is located in

either lower right or lower left

portion of the LCD indicator.

Figure 7.5

Local Operation Switch

Display the

process value

Display the

Ident number

Display the

Address

Write

Press the button

below the LCD display

(to request setting)

Select the

Address

Write

Press the button

below the LCD display

(to request writing)

Select the

Ident number

Adjust the zero

point

Automatic

transition

Turn the external

adjustment screw

Press the button

below the LCD display

(to change the screen)

Automatic

transition

Turn the external

adjustment screw

Press the button

below the LCD display

(to change the screen)

Turn the external

adjustment screw

F0706.ai

Figure 7.6

Setting flow of Local Operation

Interface

7.5.1 Zero Point Adjustment

While the process value screen is displayed, the

zero point can be adjusted by using the external

adjustment screw. The Local Operation (LOCAL_

OP_ENA) parameter can be used to enable or

disable the zero point adjustment with the external

adjustment screw. To use the external adjustment

screw, set the parameter to “Enabled” (default

setting is “Enabled”). For the setting procedure,

see subsection 5.2.1. Turn the external adjustment

screw with a flathead screwdriver to adjust

the value to zero. Turning the screw clockwise

increases the output and turning it counterclockwise

decreases the output. Zero point adjustment can be

performed with a resolution of 0.01% of the setting

range.

7.5.2 Ident Number Configuration

When the push button below the LCD display

is pressed while the process value screen is

displayed, the screen changes to the Ident number

setting screen. A four-digit value is displayed in the

middle of the screen and “IDENT” is shown below

it. Turn the external adjustment screw to select a

desired number and press the button below the

LCD display to set the number. When the number is

successfully set, “SAVED” will appear at the bottom

of the screen. If the setting is impossible or fails,

“FAILED” will appear. In this case, turn the external

adjustment screw to select a number to be set and

press the button below the LCD display again to set

the number.

F0707.ai

P SP

T

F

P SP

T

F

P SP

T

F

Figure 7.7

Setting screen of Ident Number

Configuration

7.5.3 Bus Address Configuration

When the push button below the LCD display

on the screen is pressed while the Ident number

setting screen is displayed, the screen changes

to the Bus Address setting screen. A number from

0 to 125 is displayed in the middle of the screen

(the default is 126), and “ADDRS” is shown at the

bottom of the screen. Turn the external adjustment

screw to select an address to be set and press the

button below the LCD display to set the address.

When the address is successfully set, “SAVED” will

appear at the bottom of the screen and restart. If the

setting is impossible or fails, “FAILED” will appear.

In this case, turn the external adjustment screw

to select a number to be set and press the button

below the LCD display again to set the address.

F0708.ai

P SP

T

F

P SP

T

F

P SP

T

F

Figure 7.8

Setting screen of Bus Address

Configuration