9. Parameter Lists

Note: The Write Mode column contains the modes in which each parameter is write enabled.

O/S:

Write enabled in O/S mode.

MAN: Write enabled in Man mode and O/S mode.

AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

—:

Read only.

9.1 Physical Block

Relative

Index

Index

Parameter

Write

Mode

Initial Value

Explanation

0

16

BLOCK_OBJECT

Information on this block such as Profile, Profile Rev, etc.

1

17

ST_REV

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

2

18

TAG_DESC

AUTO

PT1001

The user description of the intended application of the

block.

3

19

STRATEGY

AUTO

0

The strategy field can be used to identify grouping of block.

This data is not checked or processed by the block.

4

20

ALERT_KEY

AUTO

0

The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

5

21

TARGET_MODE

AUTO

AUTO

Set the Target of block mode to Auto or O/S according to the

write mode of the parameter to be set or changed.

6

22

MODE_BLK

AUTO

The mode parameter is a structured parameter composed

of the actual mode, the normal mode, and the permitted

mode.

7

23

ALARM_SUM

The current alarm status associated with the function block.

8

24

SOFTWARE_

REVISION

Revision number of the software of the field device.

9

25

HARDWARE_

REVISION

Revision number of the hardware of the field device.

10

26

DEVICE_MAN_ID

Yokogawa

Identification code of the manufacturer of the field device.

11

27

DEVICE_ID

EJX: EJX

EJA: EJA

Manufacturer specific identification of the field device.

12

28

DEVICE_SER_NUM

Serial number of field device.

13

29

DIAGNOSIS

0x00, 0x00, 0x00,

0x00

Detailed information of the devices, bitwise coded. More

than one message possible at once.

14

30

DIAGNOSIS_

EXTENSION

0x00, 0x00, 0x00,

0x00, 0x00, 0x00

Additional manufacture-specific information of the device,

bitwise coded.

15

31

DIAGNOSIS_MASK

Condensed Status:

0x00, 0x98, 0x0F,

0x80

Definition of supported DIAGNOSIS informatiion-bits.

0: not supported

1: supported

16

32

DIAGNOSIS_MASK_

EXTENSION

0xff, 0x3c, 0x37,

0xf2, 0x00, 0x00

Difinition of supported DIAGNOSIS_EXTENSION

information-bits.

0: not supported

1: supported

17

33

DEVICE_

CERTIFICATION

Not used for the trasnmitter.

18

34

WRITE_LOCKING

AUTO

Off

If set, no writes from anywhere are allowed, except for

to clear WRITE_LOCK. Block inputs will continue to be

updated.

0: on(Locked)

2457: off(Not Locked)

19

35

FACTORY_RESET

AUTO

1: Factory Reset

Allows a manual restart to be initiated.

1: Factory Reset (Resetting device for default values. The

Bus Address setting remains the same.)

2506: Warm start (Warm start of the device. All

parameterization remains unchanged.)

2712: Reset Address to '126' (Reset the Bus Address

only.)

20

36

DESCRIPTOR

AUTO

User difinition text (a string) to describe the device within

the application.

21

37

DEVICE_MESSAGE

AUTO

User difinable MESSAGE (a string) to describe the device

within the application or in the plant.