2 sensor transducer block, Sensor transducer block -3 – Yokogawa EJX115A User Manual

Page 63

Advertising
background image

<9. Parameter Lists>

9-3

IM 01C25T04-01EN

Relative

Index

Index

Parameter

Write

Mode

Initial Value

Explanation

72

88

PRIVATE_9

Not used for the transmitter

73

89

PRIVATE_10

Not used for the transmitter

74

90

PRIVATE_11

Not used for the transmitter

9.2 SENSOR Transducer Block

Relative

Index

Index

Parameter

Write

Mode

Initial Value

Explanation

0

16

BLOCK_OBJECT

Information on this block such as Block Tag, DD Revision,

Executiion Time etc.

1

17

ST_REV

0

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

2

18

TAG_DESC

AUTO

Space

The user description of the intended application of the

block.

3

19

STRATEGY

AUTO

0

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

4

20

ALERT_KEY

AUTO

0

The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

5

21

TARGET_MODE

AUTO

AUTO

Set the Target of block mode (MODE_BLK) to Auto or O/S

according to the write Mode of the parameter to be set or

changed.

6

22

MODE_BLK

AUTO

The mode parameter is a structured parameter composed

of the actual mode, the normal mode, and the permitted

mode.

7

23

ALARM_SUM

The current alarm status associated with the function block

8

24

SENSOR_VALUE

0

Raw sensor value. The uncalibrated measurement value

from the sensor.

9

25

SENSOR_HI_LIM

100

Sensor upper limit value.

10

26

SENSOR_LO_LIM

-100

Sensor lower limit value.

11

27

CAL_POINT_HI

O/S

100

The highest calibrated value.

12

28

CAL_POINT_LO

O/S

0

The lowest calibrated value.

13

29

CAL_MIN_SPAN

0.5

The minimum calibration span value allowed.

14

30

SENSOR_UNIT

O/S

1133: kPa

Engineering unit's index code for the calibration value.

SENSOR_UNIT must be a subset of the interchangeable

part of the Pressure unit. Please refer to ordering instruction

for the acceptable units.

15

31

TRIMMED_VALUE

Sensor value after the trim processing.

16

32

SENSOR_TYPE

126: Resonant

The type of sensor

17

33

SENSOR_SERIAL_

NUMBER

0

The serial number of sensor

18

34

PRIMARY_VALUE

Measured value and status available to the Function Block.

19

35

PRIMARY_VALUE_

UNIT

O/S

kPa

Engineering unit code for the primary value according to

PRIMARY_VALUE_TYPE.

20

36

PRIMARY_VALUE_

TYPE

O/S

0: Pressure

This parameter contains the application of the pressure

device.

0: Pressure

1: Flow

2: Level

3: Volume

128:differential pressure

129:gauge pressure

130:absolute pressure

253: Special

21

37

SENSOR_

DIAPHRAGM_

MATERIAL

O/S

Unknown

Index code for the material of the diaphragm, which comes

in contact with the process media.

22

38

SENSOR_FILL_

FLUID

O/S

Unknown

Index code for the fill fluid inside the sensor. The index code

is manufacturer specific.

24

40

SENSOR_O_RING_

MATERIAL

O/S

Unknown

Index code for the material of the o-ring between the

diaphragm and process connection.

Advertising