<9. Parameter Lists>

9-8

IM 01C25T04-01EN

9.4 AI Function Block

Relative

Index

Index

Parameter

Write

Mode

Initial Value

Explanation

0

16

BLOCK_OBJECT

Information on this block such as Block Tag, DD Revision,

Executiion Time etc.

1

17

ST_REV

0

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

2

18

TAG_DESC

AUTO

Space

The user description of the intended application of the

block.

3

19

STRATEGY

AUTO

0

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

4

20

ALERT_KEY

AUTO

0

The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

5

21

TARGET_MODE

AUTO

AUTO

Set the Target of block mode (MODE_BLK) to Auto, Man or

O/S according to the write Mode of the parameter to be set

or changed.

6

22

MODE_BLK

AUTO

The mode parameter is a structured parameter composed

of the actual mode, the normal mode, and the permitted

mode.

7

23

ALARM_SUM

The current alarm status associated with the function block

8

24

BATCH

AUTO

This parameter is intended to be used in Batch applications

in line with IEC 61512.

10

26

OUT

MAN

This parameter contains the current measurement

value from Transducer Block or configuration adjusted

engineering unit and the belonging state in AUTO MODE.

OUT contains the value and status set by an operator in

MAN MODE.

11

27

PV_SCALE

O/S

Conversion of the Process Variable into percent using the

high and low scale value.

12

28

OUT_SCALE

O/S

Scale of the Process Variable. This parameter contains the

values of the lower limit and upper limit effective range, the

code number of the engineering unit of Process Variable

and the number of digits to the right of the decimal point.

13

29

LIN_TYPE

O/S

0

Type of linearization.

0: no linearization

10: Square root

14

30

CHANNEL

O/S

AI1:

Primary Value

AI2:

Static Pressure

(H)

AI3:

Capsule

Temperature

Reference to the active Transducer Block which provides

the measurement value to the Functiion Blocks.

16

32

PV_FTIME

AUTO

0.000

Time constant of a signal exponential filter for the PV, in

seconds.

17

33

FSAFE_TYPE

AUTO

1

Defines reaction of device, if a fault is detected.

18

34

FSAFE_VALUE

AUTO

0

Defaut value for the OUT parameter, if sensor or sensor

electronic fault is detected. The unit of this parameter is the

same as that for the OUT one.

19

35

ALARM_HYS

AUTO

0.5

Amount the PV must return within the alarm limits before

the alarm condition clears. Alarm Hysteresis is expressed in

engineering unit.

21

37

HI_HI_LIM

AUTO

+1.#INF

Value for upper limit alarms.

23

39

HI_LIM

AUTO

+1.#INF

Value for upper limit warnings.

25

41

LO_LIM

AUTO

-1.#INF

Value for lower limit warnings.

27

43

LO_LO_LIM

AUTO

-1.#INF

Value for lower limit alarms.

30

46

HI_HI_ALM

State of the upper limit of alarms.

31

47

HI_ALM

State of the upper limit of warnings.

32

48

LO_ALM

State of the lower limit of warnings.

33

49

LO_LO_ALM

State of the lower limit of alarms.

34

50

SIMULATE

AUTO

Disabled

For commissioning and test purposes the input value from

the Transducer Block in the Analog input Function Block AI-

FB can be modified. That means that the Transducer and

AI-FB will be disconnected.

35

51

OUT_UNIT_TEXT

Not used for the transmitter