<10. General Specifications>

10-1

IM 01C25T04-01EN

10. General Specifications

10.1 Standard Specifications

For items other than those described below,

refer to each User’s Manual.

Applicable Model:

All DPharp EJX/EJA series.

Output:

Digital communication signal based on

PROFIBUS PA protocol.

Supply Voltage:

9 to 32 V DC for general use, flameproof type,

intrinsically safe (Ex ic), or nonincendive

9 to 24 V DC for intrinsically safe type Entity

model

9 to 17.5 V DC for intrinsically safe type FISCO

model

Communication Requirements:

Supply Voltage: 9 to 32 V DC

Current Draw: 15 mA (max)

Response Time (for Primary Value):

F, L capsule: 185 ms

M, H, A, B, C, D capsule: 150 ms

When amplifier damping is set to zero, and

including dead time.

Update Period:

Differential Pressure: 100 ms

Static Pressure: 100 ms

Capsule Temperature: 1 s

Amplifier Temperature: 1 s

Integral Indicator (LCD display):

5-digit Numerical Display, 6-digit Unit Display

and Bar graph. The indicator is configurable

to display one or up to four of the I/O signals

periodically.

Functional Specifications:

Functional specifications for PROFIBUS

communication conform to the PROFIBUS-PA

ver 3.02

Function Block:

Three AI blocks, One Totalizer block.