Handling cautions, 1 fm approval, Handling cautions -1 – Yokogawa EJX115A User Manual

Page 9: Fm approval -1, Caution, Warning, Important

Advertising
background image

<2. Handling Cautions>

2-1

IM 01C25T04-01EN

2. Handling Cautions

2.1 Installation of an Explosion-

Protected Instrument

If a customer makes a repair or modification to

an intrinsically safe or explosionproof instrument

and the instrument is not restored to its original

condition, its intrinsically safe or explosionproof

construction may be compromised and the

instrument may be hazardous to operate. Please

contact Yokogawa before making any repair or

modification to an instrument.

CAUTION

This instrument has been tested and certified

as being intrinsically safe or explosionproof.

Please note that severe restrictions apply to this

instrument’s construction, installation, external

wiring, maintenance and repair. A failure to abide

by these restrictions could make the instrument a

hazard to operate.

WARNING

Maintaining the safety of explosionproof

equipment requires great care during mounting,

wiring, and piping. Safety requirements also

place restrictions on maintenance and repair.

Please read the following sections very carefully.

WARNING

The range setting switch must not be used in a

hazardous area.

IMPORTANT

All the blind plugs which accompany the

transmitters upon shipment from the factory are

certified by the applicable agency in combination

with the transmitters. The plugs which are

marked with the symbols “◊ Ex” on their surfaces

are certified only in combination with the

transmitters.

2.1.1 FM approval

a. FM Explosionproof Type
Caution for FM Explosionproof type

Note 1. The transmitters with optional code /FF1

are applicable for use in hazardous

locations:

• Applicable Standard:

FM3600, FM3615, FM3810,

ANSI/NEMA 250

• Explosionproof for Class I, Division 1,

Groups B, C and D.

• Dust-ignitionproof for Class II/III, Division 1,

Groups E, F and G.

• Enclosure rating: NEMA 4X.

• Temperature Class: T6

• Ambient Temperature: –40 to 60°C

• Supply Voltage: 32V dc max.

• Current Draw: 15 mA dc

Note 2. Wiring

• All wiring shall comply with National Electrical

Code ANSI/NFPA70 and Local Electrical

Codes.

• When installed in Division 1, “FACTORY

SEALED, CONDUIT SEAL NOT

REQUIRED.”

Note 3. Operation

• Keep the “WARNING” nameplate attached to

the transmitter.

WARNING: OPEN CIRCUIT BEFORE

REMOVING COVER.

FACTORY SEALED, CONDUIT SEAL NOT

REQUIRED.

INSTALL IN ACCORDANCE WITH THE

USERS MANUAL IM 01C25.

• Take care not to generate mechanical

sparking when accessing the instrument and

peripheral devices in a hazardous location.

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void

Factory Mutual Explosionproof Approval.

Advertising