9 installation of explosion protected type, 1 fm approval – Yokogawa EJA438 User Manual

Page 11

Advertising
background image

IM 1C22J1-01E

2-3

2. HANDLING CAUTIONS

4) After completing the test and being very careful not

to touch exposed conductors disconnect the
insulation tester and connect a 100 k

resistor

between the grounding terminal and the short-
circuiting SUPPLY terminals. Leave this resistor
connected at least one second to discharge any
static potential. Do not touch the terminals while it
is discharging.

• Dielectric Strength Test

1) Short-circuit the + and – SUPPLY terminals in the

terminal box.

2) Turn OFF the dielectric strength tester. Then

connect the tester between the shorted SUPPLY
terminals and the grounding terminal. Be sure to
connect the grounding lead of the dielectric strength
tester to the ground terminal.

3) Set the current limit on the dielectric strength tester

to 10 mA, then turn ON the power and gradually
increase the test voltage from ‘0’ to the specified
voltage.

4) When the specified voltage is reached, hold it for

one minute.

5) After completing this test, slowly decrease the

voltage to avoid any voltage surges.

2.9 Installation of Explosion

Protected Type

NOTE

For FOUNDATION Fieldbus explosion protected
type, please refer to IM 1C22T2-01E.

WARNING

To pressure the safety of explosionproof equip-
ment requires great care during mounting,
wiring, and piping. Safety requirements also
place restrictions on maintenance and repair
activities. Please read the following sections very
carefully.

2.9.1 FM Approval

a. FM Intrinsically Safe Type

Caution for FM intrinsically safe type. (Following
contents refer “DOC. No. IFM012-A12 P.1 and 2.”)

Note 1. Model EJA Series pressure transmitters

with optional code /FS1 are applicable for
use in hazardous locations.

• Intrinsically Safe for Class I, Division 1, Groups A,

B, C & D. Class II, Division 1, Groups E, F & G
and Class III, Division 1 Hazardous Locations.

• Nonincendive for Class I, Division 2, Groups A, B,

C & D. Class II, Division 2, Groups E, F & G and
Class III, Division 1 Hazardous Locations.

• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –40 to 60

°

C

Note 2. Entity Parameters

• Intrinsically Safe Apparatus Parameters

[Groups A, B, C, D, E, F and G]
Vmax = 30 V

Ci = 22.5 nF

Imax = 165 mA

Li = 730

µ

H

Pmax = 0.9 W

* Associated Apparatus Parameters

(FM approved barriers)
Voc

30 V

Ca > 22.5 nF

Isc

165 mA

La > 730

µ

H

Pmax

0.9W

• Intrinsically Safe Apparatus Parameters

[Groups C, D, E, F and G]
Vmax = 30 V

Ci = 22.5 nF

Imax = 225 mA

Li = 730

µ

H

Pmax = 0.9 W

* Associated Apparatus Parameters

(FM approved barriers)
Voc

30 V

Ca > 22.5 nF

Isc

225 mA

La > 730

µ

H

Pmax

0.9 W

• Entity Installation Requirements

Vmax

Voc or Vt, Imax

Isc or It,

Pmax (IS Apparatus)

Pmax (Barrier)

Ca

Ci + Ccable, La

Li + Lcable

Note 3. Installation

• Barrier must be installed in an enclosure that meets

the requirements of ANSI/ISA S82.01.

• Control equipment connected to barrier must not

use or generate more than 250 V rms or V dc.

• Installation should be in accordance with ANSI/

ISA RP12.6 “Installation of Intrinsically Safe
Systems for Hazardous (Classified) Locations” and
the National Electric Code (ANSI/NFPA 70).

• The configuration of associated apparatus must be

FMRC Approved.