Operation, 1 preparation for starting operation, 1 preparation for starting op- eration – Yokogawa EJA438 User Manual

Page 26

Advertising
background image

IM 1C22J1-01E

6-1

6. OPERATION

6.

OPERATION

6.1 Preparation for Starting Op-

eration

The Model EJA438W and EJA438N diaphragm sealed
gauge pressure transmitter measures the pressure of
liquids, gases, and steam. This section describes the
operation procedure for the EJA438W as shown in
Figure 6.1.1 when measuring pressure in a tank.

(a) Confirm that there is no leak in the connecting part

of each diaphragm seal mounting flange.

(b) Turn ON power and connect the BT200.

Open the terminal box cover and connect the
BT200 to the SUPPLY + and –terminals.

(c) Using the BT200, confirm that the transmitter is

operating properly. Check parameter values or
change the setpoints as necessary.
For BT200 operating procedures, see Chapter 7. If
the transmitter is equipped with an integral
indicator, its indication can be used to confirm that
the transmitter is operating properly.

F0601.EPS

Transmitter mounting pipe
50mm (2 inches)

Capillary tube

Pressure transmitter

Diaphragm seal

Figure 6.1.1 Pressure Measurement

᭿

Confirming that Transmitter is Operating
Properly

Confirmation using the BT200

• If the wiring system is faulty, ‘communication error’

appears on the display.

• If the transmitter is faulty, ‘SELF CHECK ERROR’

appears on the display.

Communication error
(Faulty wiring)

Self-diagnostic error
(Faulty transmitter)

communication error

PARAM
C60:SELF CHECK
ERROR

DATA

DIAG

PRNT

ESC

F0602.EPS

Confirmation using the integral indicator

• If the wiring system is faulty, the display is blank.
• If the transmitter is faulty, an error number will

appear on the display according to the nature of the
error.

Self-diagnostic error
(Faulty transmitter)

F0603.EPS

NOTE

If any of the error indications above appears on
the display of the integral indicator or BT200,
refer to Subsection 7.5.2 for corrective action.

᭿

Verify and Change Transmitter Parameter
Setting and Values

The following parameters are the minimum settings
required for operation. The transmitter has been
shipped with these parameters. To confirm or change
the values, see Subsection 7.3.3.

• Measuring range........See Subsection 7.3.3 (2)
• Operation mode.........See Subsection 7.3.3 (7)