IM 1C22J1-01E

7-11

7. BRAIN TERMINAL BT200 OPERATION

(6) Unit Setup for Displayed Temperature

(D30: TEMP UNIT)

When the instrument is shipped, the temperature units
are set to

degC

. Follow the procedure below to

change this setting. Note that changing the unit here
changes the unit for

A20: AMP TEMP

(amplifier

temperature) and

A21: CAPSULE TEMP

(capsule

temperature).

• Example: Change the unit for the temperature

display.

ESC

SET
D30:TEMP UNIT
deg C
< deg C >
< deg F >

Use the or key to

select “deg F.”

Press the key twice to

enter the setting.

F0722.EPS

(7) Operation Mode Setup

(D40: REV OUTPUT)

This parameter allows the direction of the 4 to 20
mA output to be reversed with respect to input.
Follow the procedure below to make this change.

• Example: Change 4 to 20 mA output to 20 to

4 mA output.

ESC

SET
D40:REV OUTPUT
NORMAL
< NORMAL >
< REVERSE>

Use the or key

to select REVERSE.

Press the key twice to

enter the setting.

F0723.EPS

(8) Output Status Display/Setup when a CPU

Failure (D52: BURN OUT)

This parameter displays the status of 4 to 20 mA DC
output if a CPU failure occurs. In case of a failure,
communication is disabled.

Setting of HIGH or LOW is enabled. This is done
with the pin (CN4) on the CPU assembly. See
Chapter 3 for details.

Standard specifications
The parameter is set to HIGH. If a failure, the
transmitter outputs the signal of 110% or higher. The
parameter

D53: ERROR OUT

is set to HIGH from

the factory.

Optional code/C1
The parameter is set to LOW. If a failure, output
which is –5% or lower is generated. The parameter

D53: ERROR OUT

is set to LOW from the factory.

• Example: Standard specifications

pin (CN4) position: H

D52: BURN OUT

HIGH

F0724.EPS

• Example: Optional code/C1

pin (CN4) position: L

D52: BURN OUT

LOW

(9) Output Status Setup when a Hardware

Error Occurs (D53: ERROR OUT)

This parameter allows the setting of the output status
when a hardware error occurs. The following three
selections are available.

(a) HOLD; Outputs the last value held before the

error occurred.

(b) HIGH; Outputs an output of 110% when an error

has occurred.

(c) LOW; Outputs an output of –5% when an error

has occurred.

Note: A hardware error means CAP MODULE FAULT of Er.01 or

AMP MODULE FAULT of Er. 02 which are shown in 7.5.2
“Errors and Countermeasures.”)

• Example: Set the output status to LOW when

a hardware error occurs.

ESC

SET
D53:ERROR OUT
HIGH
< HIGH>
< LOW>
< HOLD>

Use the or key

to select “LOW.”

Press the key twice to

enter the setting.

F0725.EPS