7. BRAIN TERMINAL BT200 OPERATION

(12)

Test Output Setup (K10: OUTPUT X%)

This feature can be used to output a fixed current
from 3.2 mA (–5%) to 21.6 mA (110%) for loop
checks.

• Example: Output 12 mA (50%) fixed current.

ESC

SET
K10:OUTPUT X %
50.0 % ACTIVE

FEED

NO

OK

SET
K10:OUTPUT X %
0.0 %
+ 050.0

Set “50.0%.”

Press the key twice to

output a fixed current at 50%.

“Active” is displayed while this is

being executed.

Press the (OK) key to cancel

the fixed current output.

F0732.EPS

IMPORTANT

1. Test output is held for approximately 10

minutes, and then released automatically after
the time has elapsed. Even if the BT200
power supply is turned off or the communica-
tion cable is disconnected during test output,
it is held for approximately 10 minutes.

2. Press the

(OK) key to release test output

immediately.

(13)

User Memo Fields (M: MEMO)

This feature provides 5 user memo fields, each
holding up to 8 alphanumeric characters. Up to 5
items such as inspection date, inspector, and other
information can be saved in these fields.

• Example: Save an inspection date of January

30, 1995.

DATA

DIAG

PRNT

ESC

SET
M10:MEMO 1

95.1.30_

ESC

PARAM
M10:MEMO 1

M20:MEMO 2

M30:MEMO 3

Set “95.1.30” in the order of year,

month, and day.

Press the key twice to

enter the setting.

F0733.EPS

7.4 Displaying Data Using the

BT200

7.4.1 Displaying Measured Data

The BT200 can be used to display measured data.

The measured data is updated automatically every 7
seconds. In addition, the display can be updated to
the present data value at any time by pressing the

(DATA)

key. For parameters associated with the

display of measured data, see Subsection 7.3.1,
“Parameter Summary.”

• Example: Display output.

DATA

DIAG

PRNT

ESC

PARAM
A10:OUTPUT (%)

A11:ENGR.OUTPUT

A20:AMP TEMP

HOME

SET

ADJ

ESC

MENU
A:DISPLAY
B:SENSOR TYPE

F0734.EPS

Data is updated automatically
at 7-second intervals.

Display “A10: OUTPUT (%).”

PARAM
A10:OUTPUT (%)
XX.X %
A11:ENGR.OUTPUT
YY.Y %
A20:AMP TEMP
ZZ deg C

communi

7.4.2 Display Transmitter Model and

Specifications

The BT200 can be used to display the model and
specifications of the transmitter.

• Example: View transmitter model name.

HOME

SET

ADJ

ESC

MENU
A:DISPLAY
B:SENSOR TYPE

DATA

DIAG

PRNT

ESC

PARAM
B10:MODEL
EJA438W-DA
B11:STYLE NO.
S1.01
B20:LRL
– 98.07 kPa

Press .

F0735.EPS

For the associated
parameters, see Subsection
7.3.1, Parameter Summary.

Advertising