7. BRAIN TERMINAL BT200 OPERATION

(a) Follow the procedure below when setting the

present output to 0% (4 mA).

FEED

NO

OK

SET
J10:ZERO ADJ
0.0 %

CLR

ESC

SET
J10:ZERO ADJ
0.0 %
+ 000.0

Press the key twice.

Zero adjustment is completed.

Press the (OK) key.

F0728.EPS

Output is 0.5%.

A10:OUTPUT (%)
0.5 %

Output is 0%.

A10:OUTPUT (%)
0.0 %

(b) In tank level measurement, if the actual level

cannot be brought to zero for zero adjustment,
then the output can be adjusted to correspond to
the actual level obtained using another measuring
instrument such as a glass gauge.

[Example]

Measurement range: 50 to 250 kPa, Actual value:
130 kPa.

Actual value

Actual

value(%)

x 100

130–50
250–50

=

x 100=40.0%

–Measurement range lower range value

Measurement range higher range value

–Measurement range lower range value

=

(b)-1 Follow the procedure below to use

J10: ZERO

ADJ

.

CLR

ESC

SET
J10:ZERO ADJ
0.0 %
+ 040.0

Enter the present actual level, 40%.

Press the key twice.

The output is changed to 40%.

F0729.EPS

Present output is 41.0%.

A10:OUTPUT (%)
41.0 %

A10:OUTPUT (%)
40.0 %

(b)-2 Follow the procedure below to use

J11: ZERO

DEV

.

ECS

ESC

SET
J11:ZERO DEV.
2.50 %
0

Since “J11: ZERO DEV.” contains

the previous correction, obtain the

correction value by adding –1.0% to

it. 2.50% + (–1.0%) = 1.50%

Set the correction value, 1.50.

Press the key twice.

F0730.EPS

Present output is 41.0%.

Output error = 40.0 – 41.0 = –1.0%.

A10:OUTPUT (%)
41.0 %

The output is changed to 40%.

A10:OUTPUT (%)
40.0 %

SET
J11:ZERO DEV.
2.50 %
1.50

(c) Zero Point Adjustment Using the External Zero

Adjustment Screw

• Enabling/inhibiting of zero point adjustment using
the external zero-adjustment screw on the transmitter
(J20: EXT ZERO ADJ)

Follow the procedure below to enable or inhibit zero
point adjustment from the zero-adjustment screw on
the transmitter.
This is set to “ENABLE” when the instrument is
shipped.

• Example: Inhibiting zero adjustment by the

external zero-adjustment screw

ESC

SET
J20:EXIT ZERO ADJ
ENABLE
< ENABLE >
< INHIBIT>

Use the or key to

select “INHIBIT.”

Press the key twice to

enter the setting.

F0731.EPS

• Zero point adjustment using external zero-adjust-
ment screw on the transmitter

Turn the zero-adjustment screw on the outside of the
transmitter case using a slotted screwdriver. Turn the
screw to the right to increase the zero point or to the
left to decrease the zero output; the zero adjusts in
increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point
changes according to the speed at which the screw is
turned. To make fine adjustments, turn the screw
slowly; to make coarse adjustments, turn the screw
quickly.

Note: When a zero point adjustment has been made, do not turn

off the transmitter less than 30 seconds after adjustment.