Connect BRAIN TERMINAL and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0806.EPS

Is power supply

polarity correct?

Is the

diaphragm seal correctly

connected to the

process?

Refer to error message summary in
Subsection 7.5.2 to take actions.

YES

NO

NO

YES

Check/correct polarity at each terminal
from power supply to the terminal box.

Use the transmitter within the
measurement range shown on the
data plate.

Correct the connections.

NO

YES

YES

Adjust the zero point.

NO

NO

YES

Is the pressure as specified?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.

Connect BRAIN TERMINAL and check self-diagnostics.

Contact Yokogawa service personnel.

F0807.EPS

Are power

supply voltage and load

resistance correct?

Is external noise

contained in the outout?

Refer to error message summary in
Subsection 7.5.2 to take actions.

Provide lagging and/or heat insulation,
or allow adequate ventilation.

Refer to Section 8.2 when selecting
instruments for calibration.

Refer to Section 5.6 to obtain the rated
voltage and load resistance.

Avoid noise by providing complete
grounding, or using shielded wires.

Adjust the output.

Is output adjusted correctly?

Large output error.

Does the self-

diagnostic indicate the problem

location?

Is transmitter

installed where there is

marked variation in

temperature?

Is excess capillary secured?

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

Secure it so that it is not moved by
wind or vibration.

Were appropriate

instruments used for

calibration?

YES

NO

Advertising