4) output signal low cut mode setup, 5) integral indicator scale setup, See (a.) through (c.) for each setting procedure – Yokogawa EJA438 User Manual

Page 38

Advertising
background image

IM 1C22J1-01E

7-9

7. BRAIN TERMINAL BT200 OPERATION

(4) Output Signal Low Cut Mode Setup

(D10: LOW CUT, D11: LOW CUT MODE)

Low cut mode can be used to stabilize the output
signal near the zero point. The low cut point can be
set in a range from 0 to 20% of output. (Hysteresis of
cut point:

±

1%)

Select “

ZERO

” as the low cut mode.

(%)

50

10

10

0

50

Input(%)

Output

LOW CUT mode ZERO at 10%

F0716.EPS

• Example: Change the low cut setting range

from 5% to 10%, and the low
cut mode from LINEAR to ZERO.

FEED

NO

OK

SET
D11:LOW CUT MODE
ZERO

Use the or key

to select ZERO.

Press the key twice to

enter the setting.

Press the (OK) key.

F0717.EPS

FEED

NO

OK

SET
D10:LOW CUT
10.0 %

ESC

SET
C11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >

DATA

DIAG

PRNT

ESC

PARAM
D10:LOW CUT
10.0 %
D11:LOW CUT MODE
ZERO
D20:DISP SELECT
NORMAL %

CLR

ESC

SET
D10:LOW CUT
5.0 %
+ 10.0

Set “10.”

Press the key twice to

enter the setting.

Press the (OK) key.

Next, the [D11: LOW CUT MODE]

setting panel is displayed.

(5) Integral Indicator Scale Setup

The following 5 displays are available for integral
indicators.

T0708.EPS

D20: DISP SELECT

and Display

NORMAL %

USER SET

USER & %

INP PRES

PRES & %

Indicates –5 to 110% range
depending on the Measurement
range (C21, C22).

Indicates values depending on the
Engineering range (D22, D23).

(

Note 1

)

Units set using Engineering unit
(D21) are not indicated.

Indicates user set and % alternately
in 3 second intervals.

Indicates input pressure. Indication
limits –19999 to 19999.

Indicates input pressure and %
alternately in 3 second intervals.

A10:OUTPUT (%)

45.6 %

Description

and Related parameters

A11:ENGR.OUTPUT

20.0 M

A10:OUTPUT (%)

45.6 %

A11:ENGR. OUTPUT

20.0 M

A40:INPUT

456 kPa

A10:OUTPUT (%)

45.6 %

A40:INPUT

456 kPa

(Note 1) Scale range can be specified with range limit specifications up

to 5 digits (excluding any decimal point) for low or high range

limits within the range of –19999 to 19999.

See (a.) through (c.) for each setting procedure.