<A1. SAFETY INSTRUMENTED SYSTEMS INSTALLATION>

A1-5

IM 01R01B30-00E-E 5th edition February 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

A1.4 Assessment results

A1.4.1 Safety related parameters

The following results have been obtained from the assessment report Report No.: ROTA YOKOGAWA
08/07-23 R002 Version V2, Revision R1; August 2010 issued by exida.

Average PFD values have been calculated assuming a Diagnostic Coverage (DC) of 99%, a mission time
of 10 years and a Mean Time To Restoration of 24 hours.

Table 2: Summary for RAKD ([V1]) with fail-safe limit switches 3 – Failure rates

 

Profile 2

Profile 4

Fail Safe Detected (λSD)

0 FIT

0 FIT

Fail Safe Undetected (λSU)

132 FIT

174 FIT

Fail Dangerous Detected (λDD)

4 FIT

19 FIT

Fail Dangerous Undetected (λDU)

62 FIT

108 FIT

SFF

4

68.7%

64.1%

MTBF

486 years

310 years

SIL AC

5

SIL2

SIL2

Safety metrics according to ISO 13849-1

6

:

MTTF

d

(years)

1730

899

DC

6%

15%

Category (CAT)

CAT 1

CAT 1

Performance Level (required)

PL

r

= c

PL

r

= c

Performance Level (calculated)

6.60E-08 1/h

1.27E-07 1/h

T[Proof] = 1 year

T[Proof] = 5 years

T[Proof] = 10 years

PFDAVG = 2.96E-04

PFDAVG = 1.37E-03

PFDAVG = 2.72E-03