A1-6 – Yokogawa RAKD User Manual

Page 68

Advertising
background image

<A1. SAFETY INSTRUMENTED SYSTEMS INSTALLATION>

A1-6

IM 01R01B30-00E-E 5th edition February 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

Table 3: Summary for RAKD ([V1]) with standard limit switches 7 – Failure rates

 

Profile 2

Profile 4

Fail Safe Detected (λSD)

0 FIT

0 FIT

Fail Safe Undetected (λSU)

163 FIT

205 FIT

Fail Dangerous Detected (λDD)

4 FIT

19 FIT

Fail Dangerous Undetected (λDU)

101 FIT

147 FIT

SFF

4

62.4%

60.3%

MTBF

375 years

261 years

SIL AC

5

SIL2

SIL2

Safety metrics according to ISO 13849-1

6

:

MTTF

d

(years)

1730

899

DC

6%

15%

Category (CAT)

CAT 1

CAT 1

Performance Level (required)

PL

r

= c

PL

r

= c

Performance Level (calculated)

6.60E-08 1/h

1.27E-07 1/h

T[Proof] = 1 year

T[Proof] = 5 years

T[Proof] = 10 years

PFDAVG = 2.96E-04

PFDAVG = 1.37E-03

PFDAVG = 2.72E-03

Table 4: Summary for RAKD ([V2]) with fail-safe limit switches 3 – Failure rates

 

Profile 2

Profile 4

Fail Safe Detected (λSD)

0 FIT

0 FIT

Fail Safe Undetected (λSU)

162 FIT

215 FIT

Fail Dangerous Detected (λDD)

4 FIT

19 FIT

Fail Dangerous Undetected (λDU)

84 FIT

139 FIT

SFF

4

66.3%

62.7%

MTBF

399 years

259 years

SIL AC

5

SIL2

SIL2

Safety metrics according to ISO 13849-1

6

:

MTTF

d

(years)

1297

723

DC

5%

12%

Category (CAT)

CAT 1

CAT 1

Performance Level (required)

PL

r

= c

PL

r

= c

Performance Level (calculated)

8.80E-08 1/h

1.58E-07 1/h

T[Proof] = 1 year

T[Proof] = 5 years

T[Proof] = 10 years

PFDAVG = 4.01E-04

PFDAVG = 1.86E-03

PFDAVG = 3.68E-03

Advertising