2 data mapping, 1 preparation, Data mapping -4 4.2.1 – Yokogawa GC1000 Mark II Process Gas Chromatograph User Manual

Page 17: Preparation -4

Advertising
background image

<4. Engineering>

4-4

IM 11B06E01-01E

4.2

Data mapping

4.2.1

Preparation

The IP addresses of analyzers, and mapping data of the Modbus address of analyzers onto the

address of ASGW, are defined in the ASGW_MAP.CSV file.
Mapping operation is complete when the file is transferred to ASGW with FTP and the ASGW is

rebooted.
ASGW checks the file at start-up. Information of error diagnosis is confirmed with Web browser.
At the installation on ASGW a sample file is setted. Mapping operation is realized with modifica-

tion of the sample file.
The mapping file does not depend on ASGW, so that the composition of mapped file is available

in advance without ASGW.

#SLAVE, 1
#RETRY, 3

**** Station
#STN,

10,

GC1000,

192.168.0.10,

GC1000Mk2 at SiteA

#STN,

42,

GC1000,

192.168.0.42,

GC1000Mk2 at SiteB

#STN, 101, ASIU,

192.168.0.101, ASIU

#STN, 252, PCAS,

192.168.0.252, PCAS

**** Mapping
#MAP, 10, 1001,

1,

RUN

#MAP, 42, 1002,

1,

RUN

#MAP, 10, 1004,

2,

STOP

#MAP, 42, 1005,

2,

STOP

#MAP,

252,

11001,

11010,

ID=10 A-ch Normal

#MAP,

252,

11002,

11042,

ID=42 A-ch Normal

#MAP,

252,

11004,

11310,

ID=10 B-ch Normal

#MAP,

252,

11005,

11342,

ID=42 B-ch Normal

#MAP,

101,

31002,

30401,

AI value of ASIU

**** Alarm DO ouput
#DO,

10,

ALM_LVL1,

12,

DO_12 output for alarm of Stn10

#DO,

10,

ALM_LVL2,

13,

DO_13 output for alarm of Stn10

#DO,

42,

ALM_LVL1,

3,

DO_3 output for alarm of Stn42

Example of mapping file

4th Edition : Nov. 22, 2011-00

Advertising