<4. Engineering>

4-14

IM 11B06E01-01E

4th Edition : Nov. 22, 2011-00

TIP

IP address of ASGW in the redundant network must be set up from 192.168.0.1 to 192.168.0.126.

4.3.2

Modification of serial port setting

In the case of using the Modbus RTU as external interface of ASIU/ASGW, this operation is

required.
ASGW has two communication ports and both initial setting data are as follows.

Baudrate =9600

DataBitLength =8

StopBitLength =1

Parity

=NONE

After ASIU/ASGW mode is changed to maintenance mode, the communication port is set with

the maintenance window on web browser.
Refer to the guide of STARDOM FCN/FCJ (IM 34P02Q01-01E) about the method of modifica-

tion.
Setting parameters are “COM1 Port Setting File” or “COM2 Port Setting File”.

4.3.3

Allocating DO information

Allocate the device label of ASGW to the DO terminal before outputting DO information of the

ASGW application to the terminal. The device label of ASGW is the default factory setting.

(1) Confirming the current state of the ASGW application

Confirm that the ASGW application has been successfully downloaded. After connecting by using

Resource Configurator, click the ControlApplication/DevLabelVar. Then, confirm that the value

of I/O Category is O_Sts and the value of Device Label is Q_D_17 to Q_D_32, as shown in the

following figure.