T QUASAR Flare Monitors Operation Manual

Operating the M8100FM-EXP 40

3. Adjust the System Gain no more than 2 turns counter-clockwise so that the analog meter

reads .35. Once adjusted, the red “Flame Out Alarm” LED should light after the expected
delay. If this does not occur, proceed to step 5 below.

4. Verify that the analog meter reads at least .8 when the Flare is present. The procedure is

complete. (Do not proceed to step 5.)

5. Adjust the set-point pot (Figure 11, Item 10) to be above the unacceptable condition

observed in step 4 by .2 divisions on the meter.
a. Move the Gain/Setpoint Switch (Item 6) to the Setpoint position.
b. Adjust the setpoint as required; verify the Alarm LED lights.
c. Return the Gain/Setpoint switch to the Gain position.
d. Return to step 4 above.