Tork k-seasonal, Digital time switches & energy management controls, Photoelectric control interface – NSi Industries K801Z User Manual

Page 23: Momentary contact

Advertising
background image

TORK DIGITAL TERMINAL BLOCK

NO

C

NC

120/240V LINE

277/480V

40 AMP/POLE

WHITE

120 /240V

LINE

LOAD

PHOTOCONTROL

RED

BLACK

L

N

120VAC

COIL

5401

CONTACTOR

TORK TIME CONTROLLER

NO

C

NC

H

120 VAC

OPEN

TIME SWITCH

OUTPUT

NO

C

NC

24-277VAC

NO

C

NC

SMC3D

PUSH

ON

PUSH

OFF

N

CLOSED

N

LOW VOLTAGE LATCHING
RELAY OR MECHANICALLY-
HELD CONTACTOR.

22

TORK K-SEASONAL

DIGITAL TIME SWITCHES & ENERGY MANAGEMENT CONTROLS

RELAY OR CONTACTOR SWITCHING

LINE VOLTAGE SWITCHING LOAD DIRECT

TORK DIGITAL CONTROL

TERMINAL BLOCK

Mechanically-
held contactor
self clearing

Electrically-
held contactor

120/240V LINE
277/480V
40 AMP/POLE

LINE

OPEN

LOAD

TORK MODELS 5401 & 5441

OR SUITABLE SUBSTITUTES

CLOSE

C

120VAC COIL

NEUTRAL

120 VAC

NO

C

NC

TORK DIGITAL TERMINAL BLOCK

NO

C

NC

10 AMP MAX.

NEUTRAL

120 /240VAC

LOAD

PHOTOELECTRIC CONTROL

INTERFACE

Tork Model 2101 — Conduit Mount

Tork Model 5021S with 2421 — Bracket Mount

Model 5401 — DPST

To control lighting circuits where a Photoelectric control
turns “ON” at dusk and “OFF” by preset times of 120VAC
controller. Controller can be set to turn “ON” early a.m.
before dawn, and have Photoelectric control turn “OFF” at
dawn . . . turn back “ON” at dusk, and controller turns lights
“OFF” during nights when lighting is no longer needed.

Photoelectric control can be wired directly to 120VAC
control circuits.

MOMENTARY CONTACT

Tork Model SMC-3D

The SMC-3D will operate low voltage latching relays or
mechanically-held contactors with or without remote manual
push button override.

The adapter converts a constant applied 120VAC (input) to
a 2 second contact closure at the “ON relay” output closing
common and normally open (C, NO). When the constant
applied 120VAC input opens, a 2 second contact closure at
the “OFF relay” output between common and normally open
(C, NO) occurs. The SMC-3D can be operated by any
TORK Time Controller or a remote manual SPST standard
constant “ON-OFF” switch.

The SMC-3D will pulse “ON” an electrically-held contactor or
motor starter with self contained “ON-OFF” push buttons.
“ON” relay will pulse 2 second “ON” and electrically hold the
contactor “ON”. By interrupting the holding circuit of the
contactors “OFF” button across common and normally
closed (C, NC) of the SMC-3D “OFF” relay the 2 second
opening of common and normally closed (C, NC) will allow
the electrically held contactor to open, thereby going “OFF”.

FIG. 2

FIG. 3

FIG. 4

FIG. 1

MOMENTARY CONTACT ADAPTER

FOR USE WITH MECHANICALLY-HELD CONTACTORS