Tork k-seasonal, Tork, Digital time switches & energy management controls – NSi Industries K801Z User Manual

Page 27

Advertising
background image

15"

4"

10"

TORK

1

SUN

2

MON

3

TUE

4

WED

5

THU

6

FRI

7

SAT

8

HOL

9

EXIT

0

AM/PM

YES

NO

REVERSE

ENTER

A typical wiring diagram of
how to use K-Seasonal for
night set-back for heating or
night set-up for cooling.

Winter Set-back: Set 2-wire
night thermostat at 55°F.
When control is “OFF”
temperature will not go
below 55°.

When control is “ON ” (day
hours) day thermostat set at
70° to 72° will override night
thermostat.

Summer Set-up: Night
thermostat is usually set at
90° to 95°. When control
turns “ON”, day thermostat
will override night setting and
cool to (76° to 78°) day
setting.

26

TORK K-SEASONAL

DIGITAL TIME SWITCHES & ENERGY MANAGEMENT CONTROLS

TYPICAL CONNECTION FOR TORK DIGITAL TIME SWITCH AND

DAY/NIGHT THERMOSTAT WITH HVAC EQUIPMENT

FIG. 9

FIG. 7

TORK DIGITAL TERMINAL BLOCK

NO

C

NC

POWER

24 VOLTS

LOW VOLTAGE

CONTROL POWER
FROM HVAC UNIT

24 Volts
Two Wire
Night
Thermostat
(Time Switch
Circuit OFF)

Day Thermostat

4-Wire Heat/Cool Thermostat

(Time Switch Circuit ON)

HEAT

COOL

FAN

WHITE

YELLOW

GREEN

RED

1

SUN

2

MON

3

TUE

4

WED

5

THU

6

FRI

7

SAT

8

HOL

9

EXIT

0

AM/PM

YES

NO

REVERSE

ENTER

FIG. 8

Advertising