3.4 Maintenance manager / Error list

With one or several errors, the extended operating level
always starts with the error list. Signalling an actual entry
in the error list (alarm, error) is done by the Err LED in
the display. To reach the error list press Ù twice.

Error list:

Operation

Maintenance manager / Error list

12

Operating KS4x-1

125

126

SP.x

run

Ada

Err

Err LED status

Signification

Proceed as follows

blinks

(Status

2)

Alarm due to existing

error

- Determine the error type in the error list via the

error number

- -Change to status

1 after error removal.

lit

(Status

1)

Error removed,
Alarm not acknowledged

- Acknowledge the alarm in the error list pressing

key È or Ì

- The alarm entry was deleted (Status

0) .

off

(Status

0)

No error,
all alarm entries deleted

-Not visible except when acknowledging

Name

Description

Cause

Possible remedial action

E.1

Internal error,
cannot be removed

- E.g. defective EEPROM

- Contact PMA service
- Return unit to our factory

E.2

Internal error, can be

reset

- e.g. EMC trouble

- Keep measurement and power supply

cables in separate runs

- Ensure that interference suppression of

contactors is provided

E.4

Hardware error

- Codenumber and hardware

are not identical

- Contact PMA service
- Elektronic-/Optioncard must be

exchanged

FbF.1

Sensor break INP1

- Sensor defective
- Faulty cabling

- Replace INP1 sensor
- Check INP1 connection

Sht.1

Short circuit INP1

- Sensor defective
- Faulty cabling

- Replace INP1 sensor
- Check INP1 connection

POL.1

INP1polarity error

- Faulty cabling

- Reverse INP1 polarity

FbF.2

Sensor break INP2

- Sensor defective
- Faulty cabling

- Replace INP2 sensor
- Check INP2 connection

Sht.2

Short circuit INP2

- Sensor defective
- Faulty cabling

- Replace sensor INP2
- Check INP2 connection

POL.2

INP2 polarity

- Faulty cabling

- Reverse INP2 polarity

HCA

Heating current alarm

(HCA)

- Heating current circuit

interrupted, I<

HC.A or I>

HC.A (dependent of
configuration)

- Heater band defective

- Check heating current circuit
- If necessary, replace heater band

SSr

Heating current short

circuit (SSR)

- Current flow in heating

circuit with controller off

- SSR defective

- Check heating current circuit
- If necessary, replace solid-state relay