11

Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 14 bits

Decimal point:

0 to 3 digits behind the decimal point

Dig. input filter:

adjustable 0,000...9999 s

Scanning cycle:

100 ms

Measured value
correction:

2-point or offset correction

Thermocouples

r

Table 1 (page 53 )

Input resistance:

³1 MW

Effect of source resistance:

1

mV/W

Cold-junction compensation

Maximal additional error:

± 0,5 K

Sensor break monitoring

Sensor current:

£ 1 mA

Configurable output action

Resistance thermometer

r

Table 2 (page 53 )

Connection:

2 or 3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break and short circuit

Special measuring range
BlueControl (engineering tool) can be used to
match the input to sensor KTY 11-6
(characteristic is stored in the controller).

Physical measuring range:

0...4500 Ohm

Linearization segments

16

Current and voltage signals

r

Table 3 (page 53 )

Span start, end of
span:

anywhere within measuring
range

Scaling:

selectable -1999...9999

Linearization:

16 segments, adaptable with
BlueControl

Decimal point:

adjustable

Input circuit monitor: 12,5% below span start (2mA, 1V)

SUPPLEMENTARY INPUT INP2

Resolution:

> 14 bits

Scanning cycle:

100 ms

Accuracy:

< 0,5 %

Heating current measurement

via current transformer (

® Accessory equipment)

Measuring range: 0...50mA AC
Scaling:

adjustable -1999...0,000...9999 A

Current measuring range

Technical data as for INP1

CONTROL INPUT DI1

Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.

Switched voltage:

2,5 V

Current:

50

mA

CONTROL INPUTS DI2, DI3 (OPTION)

Configurable as switch or push-button!
Optocoupler input for active triggering

Nominal voltage

24 V DC external

Current sink (IEC 1131 type 1)
Logic “0”

-3...5 V

Logic “1”

15...30 V

Current requirement

approx.. 5 mA

TRANSMITTER SUPPLY U

T

(OPTION)

Power:

22 mA /

³18 V

If the universal output OUT3 is used there may
be no external galvanic connection between
measuring and output circuits!

GALVANIC ISOLATION

Safety isolation
Function isolation

OUTPUTS

RELAY OUTPUTS OUT1, OUT2

Contact type:

2 NO contacts with common
connection

Max. contact rating: 500 VA, 250 V, 2A at 48...62Hz,

resistive load

Min. contact rating: 6V, 1 mA DC

Technical data

Operating KS4x-1

51

Power supply

connections

Process value input INP1
Supplementary input INP2
Digital input di1

Relay outputs OUT 1,2

RS422/485 interface

Relay output OUT3

Digital inputs di2, 3
Universal output OUT3
Transmitter supply U

T