5.2 Parameters

Parameter setting level

Operating KS4x-1

38

Parameters

Cntr

Name

Value range Description

Default

Pb1

1...9999 1

Proportional band 1/2 (heating) in phys. dimensions (e.g. °C)

100

Pb2

1...9999 1

Proportional band 2 (cooling) in phys. dimensions (e.g. °C)

100

ti1

1...9999

Integral action time 1 (heating) [s]

180

ti2

1...9999

Integral action time 2 (cooling) [s]

180

td1

1...9999

Derivative action time 1 (heating) [s]

180

td2

1...9999

Derivative action time 2 (cooling) [s]

180

t1
t2

0,4...9999

Minimal cycle duration 1/2 (heating/cooling) [s]. The minimum

impulse is 1/4 x t1/t2

10

SH

0...9999

Dead zone or switching differential for on-off control [phys.

dimensions)

2

d.SP

-1999...9999

Trigger point speration for series contact

D / Y / Off [phys.

dimensions]

100

tP

0,1...9999

Minimum impulse [s]

OFF

tt

3...9999

Actuator response time for servo-motor [s]

60

Y2

-120...120

2. correcting variable

0

Y.Lo

-120...120

Lower output limit [%]

0

Y.Hi

-120...120

Upper output limit [%]

100

Y.0

-120...120

Working point for the correcting variable [%]

0

Ym.H

-120...120

Limitation of the mean value Ym [%]

5

L.Ym

0...9999

Max. deviation xw at the start of mean value calculation [phys.

dimensions]

8

1

Valid for

ConF/ othr/ DP = 0. At DP = 1/ 2/ 3 also 0,1 / 0,01 / 0,001.

SEtP

Name

Value range Description

Default

SP.LO

-1999...9999

Set-point limit low for Weff

0

SP.Hi

-1999...9999

Set-point limit high for Weff

900

SP.2

-1999...9999

Set-point 2.

0

r.SP

0...9999

Set-point gradient [/min]

OFF

t.SP

0...9999

Timer time [min]

5

SP

-1999...9999

Set-point (only visible with BlueControl!)

0

ProG

Name

Value range Description

Default

SP.01

-1999...9999

Segment end set-point 1

100 1

Pt.01

0...9999

Segment time 1 [min]

10 2

SP.02

-1999...9999

Segment end set-point 2

100 1

Pt.02

0...9999

Segment time 2 [min]

10 2

SP.03

-1999...9999

Segment end set-point 3

200 1

Pt.03

0...9999

Segment time 3 [min]

10 2