Name

Value range Description

Default

SP.E

Switching to external setpoint SP.E

0

0

no function (switch-over via interface is possible)

1

active

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

Y2

Y/Y2 switching

0

0

no function (switch-over via interface is possible)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

6

Ò key

mAn

Automatic/manual switching

0

0

no function (switch-over via interface is possible)

1

always activated (manual station)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

6

Ò key

C.oFF

Switching off the controller

0

0

no function (switch-over via interface is possible)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

6

Ò key

m.Loc

Blockage of hand function

0

0

no function (switch-over via interface is possible)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

Err.r

Reset of all error list entries

0

0

no function (switch-over via interface is possible)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

6

Ò key

P.run

Programmer Run/Stop (see page 44)

0

0

no function (switch-over via interface is possible)

2

DI1

3

DI2 (only visible with OPTION)

4

DI3 (only visible with OPTION)

di.Fn

Function of digital inputs (valid for all inputs)

0

0

direct

1

inverse

2

toggle key function

fDI1

Forcing di1 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

Advertising