The variable to be monitored can be selected separately per configuration for
each alarm.
The following variables are available (

ConF / Lim / Src .x ):

Variable (

Src .x) Remark

Alarm type

Process value

Absolute

Control deviation

xw

Process value - effective set-point. The effective set-point Weff

is used. E.g with a ramp, this is the changing set-point rather

than the target set-point

.

Relative

Control deviation

xw + suppression

after start-up or

set-point change

with time limit

The alarm output is suppressed after switch-on or after a

set-point change, until the process value is within the limits

for the first time. At the latest after elapse of time 10 x

ti1

the alarm is activated (

ti1 = integral time 1; parameter r

Cntr). If ti1 is switched off (ti1 = OFF), this is

considered as Î , i.e. the alarm is not activated before the

process value was within the limits once

.

Relative

Effective set-point

Weff

The effective set-point Weff for control.

Absolute

Correcting

variable y

y = controller output signal

Absolute

Deviation from SP

internal

Process value - internal set-point. The internal set-point is

used. E.g. with a ramp, this is the target set-point instead of

the varying effective set-point Weff.

Relative

Control deviation

xw + suppression

after start-up or

set-point change

without time limit

After switch-on or after a set-point change, the alarm output

is suppressed , until the process value is within the limits for

the first time

.

Relative

g

During alarm configuration, the following functions can be selected
(

ConF / Lim / Fnc.x ):

Function (

Fnc.x)

Remark

Switched off

No limit value monitoring.

Measured value

Process value monitoring. When exceeding the limit, an alarm is

generated.The alarm is reset automatically, when the process value is "within

the limits" (including hysteresis) again.

Measured value +

latch

Process value monitoring + latching of the alarm condition. When exceeding

the limit value, an alarm is output. A latched alarm persists, until it is reset

manually

.

Operation

Alarm handling

26