2 parameters 49, Parameters 49 - 51, Par.2 – West Control Solutions Pro-8 User Manual

Page 49: Setp, Prog, Parameter setting level

Advertising
background image

PAr.2

Name

Value range Description

Default

Pb12

1...9999 1

Proportional band 1 (heating) in phys. dimensions (

e.g. °C), 2. parameter set

100

Pb22

1...9999 1

Proportional band 2 (cooling) in phys. Dimensions

(e.g. °C), 2. parameter set

100

Ti22

0...9999

Integral action time 2 (cooling) [s], 2. parameter set

180

Ti12

0...9999

Integral action time 1 (heating) [s], 2. parameter set

180

Td12

0...9999

Derivative action time 1 (heating) [s], 2. parameter set

180

Td22

0...9999

Derivative action time 2 (cooling) [s], 2. parameter set

180

SEtP

Name

Value range Description

Default

SP.LO

-1999...9999

Set-point limit low for Weff

0

SP.Hi

-1999...9999

Set-point limit high for Weff

900

SP.2

-1999...9999

Set-point 2.

0

r.SP

0...9999

Set-point gradient [/min]

OFF

SP.bo

-1999...9999

Boost set-point

30

t.bo

0...9999

Boost time

10

Y.St

-120...120

Start-up setpoint (see page 56)

20

SP.St

-1999...9999

Set-point for start-up

95

t.St

0...9999

Start-up hold time (see page 56)

10

SP

-1999...9999

Set-point (only visible with BlueControl!)

0

g

SP.Lo and SP.hi should be between the limits of rnGH and rnGL see
configuration r controller page 29

ProG

Name

Value range Description

Default

SP.01

-1999...9999

Segment end set-point 1

100 1

Pt.01

0...9999

Segment time 1 [min]

10 2

SP.02

-1999...9999

Segment end set-point 2

100 1

Pt.02

0...9999

Segment time 2 [min]

10 2

SP.03

-1999...9999

Segment end set-point 3

200 1

Pt.03

0...9999

Segment time 3 [min]

10 2

SP.04

-1999...9999

Segment end set-point 4

200 1

Pt.04

0...9999

Segment time 4 [min]

10 2

1 If SP.01 … SP.04 = OFF then following parameters are not shown
2 If segment end set-point = OFF then the segment time is not visible

Parameter setting level

Pro-8

49