3 ks50/52-1 as modbus master 59, Modbus master 59, In.16 in 1 – West Control Solutions Pro-8 User Manual

Page 59: Ou.1 ou.16

Advertising
background image

8.4 Linearization

Linearization for input INP1
Access to table “

Lin” is always with selection of sensor type S.TYP = 18:

special thermocouple in INP1, or with selection of linearization

S.Lin 1: special

linearization.
Dependent of input type, the input signals are specified in µV or in Ohm
dependent of input type.

With up to 16 segment points, non-linear signals can be simulated or linearized.
Every segment point comprises an input (

In.1 … In.16) and an output (Ou.1

Ou.16). These segment points are interconnected automatically by means of

straight lines.

The straight line between the first two segments is extended downwards and the
straight line between the two largest segments is extended upwards.

I.e. a defined output value is also provided for each input value.
When switching an

In.x value to OFF, all other ones are switched off.

Condition for these configuration parameters is an ascending order.
In.1 < In.2 < ...< In.16 and Ou.1 < Ou.2 ...< Ou.16.

Special functions

Pro-8

59

Linearization

In.16

In 1

.
.
.
.
.
.

Ou.1

Ou.16

.....................

Advertising