5.3 Input scaling

When using current or voltage signals as input variables for

InP.1 or InP.2,

scaling of input and display values at parameter setting level is required. Specifi-
cation of the input value for lower and higher scaling point is in the relevant elec-
trical unit (mA/ V).

5.3.1

Input

Inp.1

g

Parameters

InL.1 , OuL.1, InH.1 and OuH.1 are only visible if

ConF / InP.1 / Corr = 3 is chosen.

In addition to these settings,

InL.1 and InH.1 can be adjusted in the range

(0...20mA / 0...10V) determined by selection of

S.tYP .

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings of

InL.1 and OuL.1 as well as of InH.1

and

OuH.1 must correspond.

5.3.2

Input

InP.2

In addition to these settings,

InL.2 and InH.2 can be adjusted in the range

(0...20/ 50mA) determined by selection of

S.tYP.

Parameter setting level

Operating manual Pro-8

51

Input scaling

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x

S.tYP

Input signal

InL.1

OuL.1

InH.1

OuH.1

30

(0...20mA)

0 … 20 mA

0

-1999...9999

20

-1999...9999

4 … 20 mA

4

-1999...9999

20

-1999...9999

40

(0...10V)

0 … 10 V

0

-1999...9999

10

-1999...9999

2 … 10 V

2

-1999...9999

10

-1999...9999

S.tYP

Input signal

InL.2

OuL2

InH.2

OuH.2

30

0 … 20 mA

0

-1999...9999

20

-1999...9999

31

0 … 50 mA

0

-1999...9999

50

-1999...9999