Constant period 40, Configuration level – West Control Solutions Pro-8 User Manual

Page 40

Advertising
background image

very weak. Moreover, the correcting variable increases very quickly to max. possi-
ble cooling. Parameter

F.H2O can be used for changing the characteristic curve.

The standard method (see section 4.4.1) is also used for heating. Cooling is also
enabled dependent of process temperature .

Parameters to be adjusted:

E.H2O: min. temperature for water cooling

(

PArA / Cntr)

t.on:

Pulse duration water cooling

t.off: min. pause water cooling

F.H2O: adaptation of (non-linear) characteristic

Water cooling

4.4.4

Heating and cooling with constant period (

CyCl= 3 )

The adjusted cycle times

t1 and t2

are met in the overall output range .
To prevent unreasonably short pulses,
parameter

tp is used for adjusting

the shortest pulse duration. With small
correcting values which require a pul-
se shorter than the value adjusted in
tp, this pulse is suppressed. Howe-
ver, the controller stores the pulse and
totalizes further pulses, until a pulse
of duration

tp can be output.

Parameters to be adjusted:

t1 : Min. cycle time 1 (heating) [s]

(

PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

tp:

min. pulse length [s]

Configuration level

Cooling functions

40

Pro-8

0

10

20

30

40

50

60

70

-100

-95

-90

-85

-80

-75

-70

-65

-60

-55

-50

-45

-40

-35

-30

-25

-20

-15

-10

-5

Controller output [%]

Water cooling non-linear,

=1

F.H2O

Water cooling non-linear,

=2

F.H2O

Water cooling non-linear,

=0,5

F.H2O

Water cooling linear

Parameter:
t.on = 0.4 sec
t.off = 0.2 sec

Effective

controller

output

50%

50%

t1 t2

/

tp

tp

30%

70%

20%

80%

10%

90%

t1 t2

/