West Control Solutions MRC 5000 Recorder Manual User Manual

Page 17

Advertising
background image

17

4.1 HARDWARE SELECTIONS - INPUT JUMPER POSITIONS

Hardware jumpers JU1 and JU2 are used to select the input type for Pen 1 and Pen 2 respectively. The jumper positions are
shown on the main wiring label on the recorder as well as on the Short Form Programming Card. See below:

JU1 and JU2 Positions - JU1 is located between wiring terminals TB2 and TB3 on the edge of the main board. JU2 is located
between wiring terminals TB3 and TB4 on the same board.

RTD and Millivolt

5 VDC

Milliamp

Thermocouple

4.2 RECORDER PROGRAMMING

The recorder setup programming can only be accomplished when the MODE slide switch is placed in the PROG/TEST/CAL
position. This switch is located to the left of the display. The Program mode is used to select: chart rotation speed, input
types/ranges, display scaling, and display options, chart scaling, and alarm operation.

In the Program/Test/Calibration mode, the keys will function as follows:

SCROLL

When a mode or section designation is displayed, SCROLL steps to the next mode or section.
When a parameter code is displayed, SCROLL will display the corresponding parameter value.
When a parameter value setting is displayed, SCROLL will display the next parameter code.

DOWN ARROW When a mode or section designation is displayed, DOWN will enter that mode or section.

When a parameter code is displayed, DOWN will display the next parameter code.
When a parameter setting is displayed, the setting will be decremented or changed, unless it is at its limit.

UP ARROW

When a mode designation is displayed, the UP key will have no effect, as the instrument is at the initial level.

Use the MODE switch to return to normal operation.

When a section designation is displayed, the UP key will revert to the mode designation.
When a parameter code is displayed, UP will revert back to the section designation.
When a parameter setting is displayed, the setting will be incremented or changed, unless it is at its limit.

To enter the Program/Test/Cal mode, position the MODE switch accordingly. The unit will display Prog. Subsequent
depressions of the SCROLL key will cause the unit to display tESt, and then

CAL

, and back to Prog.

NOTE: When the MODE switch is placed in the PROG/TEST/CAL position, all alarm LEDs will be turned off and all
relays will be deenergized.

To enter the Program mode, press the DOWN arrow key when Prog is displayed.

The display will show PEn1 (Pen 1 parameters). Subsequent depressions of the SCROLL key will show PEn2 (Pen 2
parameters, if Pen 2 exists), CHAr (Chart operation), CP (Comms parameters, if optional communications is installod) and
then back to PEn1.