4.3 TEST MODE - TEST

To enter the Test mode, press SCROLL until tESt shows on the display. Press DOWN to enter the Test mode. Press
SCROLL to display the various tests (diSP and Chrt). Press DOWN to enter a test section.

4.3.1 Display, Keypad, and Relay Test

- diSP

Once you enter the Display/Keypad/Relay test by depressing DOWN, the display should first show all 8s with decimal points
and all status LEDs lit for about 5 seconds. Then the display will go blank for 5 seconds.

Then the display will show SCrL. Depress the SCROLL key to proceed with the keypad test.

The display will show UAro. Depress the UP arrow key to proceed with the keypad test.

The display will show dAro. Depress the DOWN arrow key to complete the keypad test.

The display will show rLy while the instrument does the relay test. Each alarm relay will be energized in sequence for about 4
seconds while its status LED (ALRM 1/1, ALRM 1/2, ALRM 2/1, or ALRM 2/2) is lit. When complete, rLy will be displayed for
4 seconds and then diSP will be displayed.

4.3.2 Chart Test -

Chrt

Running the Chart Test will produce a test pattern drawn by the pens on the chart with the chart advancing.

After entering the test by pressing DOWN, the green pen will go toward the home position and the red pen will go toward the
outside of the chart. The chart will rotate at roughly 1 revolution every 1.5 minutes. Both pens will travel about 80% of the
chart in about 15 seconds, and then reverse their travel, and return to their initial position. This process will continue to be
repeated.

Depress any key to terminate the Chart test. The pen(s) will go to the home position and then Chrt will be displayed.

Advertising