Construction, Evironmental and operating conditions, Digital communicatons – West Control Solutions MRC 5000 Recorder Manual User Manual

Page 27: General reference data, Approvals and compliance

Advertising
background image

27

CONSTRUCTION

Enclosure

Injection molded Noryl case and cover with acrylic window

NEMA Rating

NEMA 3 standard, NEMA 4X optional

Conduit Openings

Three openings on the right side

Mounting

Panel or wall

Overall Dimensions

14" wide X 14" high X 3.8" deep.
(355.6mm X 355.6mm X 96.5mm)

Panel Cutout

12.7" wide X 12.7" high
(322.58mm X 322.58mm)

Panel Depth

2.5" (63.5mm)

Panel Protrusion

1.3" (33.0mm)

Weight

7 lbs maximum

Retrofit

With adaptor plate, will fit Partlow MRC 7000/ARC 4100 cutout

EVIRONMENTAL AND OPERATING CONDITIONS

Operating Temperature

0

°C to 55°C (32°F to 122°F)

Storage Temperature

-40

°C to 65°C (-4°F to 149°F)

Humidity

10 to 90% RH, non-condensing

Vibration

0.3 to 100 Hz @ 0.2g

Mounting Position

Up to 30

° forward or backward tilt from vertical

Up to 10

° side tilt from vertical

DIGITAL COMMUNICATONS

Configuration Port

TTL levels

Communications Port

RS-485 serial communications, Half-duplex

Protocol

MODBUS RTU

Bit Rate

9600 bits per second

Parity

Odd

Address

User configurable - 0 to 247

GENERAL REFERENCE DATA

Data Backup

EEPROM for configuration parameters and calibration data
EEPROM for alarm setpoints

Warranty

Two years

APPROVALS AND COMPLIANCE

Safety

UL Approved for USA - UL 1092, UL 916, and QUXY - File E67237
UL Certified for Canada - CSA Spec 142 - File E67237
CE - Complies with EN 61010-1:1993: A2-1995

Immunity/Susceptability

CE - Complies with EN50082-2

Emissions

CE - Complies with EN50081-1: 1992 and EN50081-2:1994: EN55022 Class B

Limit Device

FM: Approved

Advertising