To enter the desired section of the Program mode, press the DOWN arrow key when the desired section is displayed.

Use the keys as defined previously to enter modes and sections, move around, and modify parameter settings. The param-
eters, their definitions, and range of adjustment, are as follows:

PEN 1 AND PEN 2 SECTIONS OF PROGRAM MODE

- PEn1 and PEn2

(Pen 2 will appear only if present in the recorder.)
These parameters apply to each pen, assuming pen 2 is present, and are configured in each respective section.

PARAMETER

PARAMETER

DEFAULT

CODE

DESCRIPTION

SETTINGS OR RANGE

SETTING

InPS

Input Selection

0 - 18

1

0 = J T/C 0 to 760

°C

1 = J T/C 0 to 1400

°F

2 = K T/C 0 to 1360

°C

3 = K T/C 0 to 2500

°F

4 = T T/C -200 to 400

°C

5 = T T/C -330 to 750

°F

6 = R T/C 200 to 1650

°C

7 = R T/C 400 to 3000

°F

8 = S T/C 200 to 1650

°C

9 = S T/C 400 to 3000

°F

10 = RTD 100 ohm -140 to 400

°C

11 = RTD 100 ohm -200 to 750

°F

12 = 0-20mA
13 = 4-20mA
14 = 0-50mV
15 = 10-50mV
16 = 0-25mV
17 = 0-5VDC
18 = 1-5VDC

ICor

Input Correction

-999 to 999*

0

(calibrates sensor to
recorder)

A1

Alarm Type

OFF = none

OFF

(will show only if present)

Hi = High Alarm
Lo = Low Alarm
HL = High Limit
LL = Low Limit

A2

Alarm Type

OFF = none

OFF

(will show only if present)

Hi = High Alarm
Lo = Low Alarm
HL = High Limit
LL = Low Limit

dISP

Display Input/Pen Value

On = Display value

On

during normal operation,

OFF = Do not display value

RUN mode

dPOS

Decimal Point Position

0 = nnnn

0

1 = nnn.n
2 = nn.nn

EUU

Engineering Units that

-9999 to 9999*

5000

equate to upper
transducer input
(will show only for Volt