Performance Data

ESEER CALCULATIONS

The quoted EER figures (

General Specification

, on page 29) cover the performance of the

unit ONLY at the standard rating conditions of 7/12°C water, 35°C ambient. The ESEER
calculation method has been developed by Eurovent to give a single value that is a
realistic indication of the efficiency of the chiller across the whole range of operation.

The ESEER value is calculated from the unit’s performance at 20, 25, 30 and 35°C
ambient temperatures for all loading stages, and with a fixed 7°C supply temperature. All
calculations assume the system operates with 100% water.

ESEER = A.EER

100%

+ B.EER

75%

+ C.EER

50%

+ D.EER

25%

A, B, C and D are weighting factors 0.03, 0.33, 0.41 and 0.25.

Temperature

20°C

25°C

30°C

35°C

Capacity Requirement

25%

50%

75%

100%

Percentage of Total Hours

0.25

0.41

0.33

0.03


FSEER CALCULATIONS
(Free Cooling)

Whilst the ESEER is useful for providing a true energy efficiency of a unit’s performance
over a year it does not offer any advantages for use of free-cooling which can significantly
reduce the unit’s lifecycle power consumption.

The FSEER calculation method has been developed by Airedale to give a single value
that is a realistic indication of the efficiency of the chiller across the whole range
of operation.

The quoted Airedale FSEER figures (

General Specification

, on page 29) are similar to the

ESEER and includes the unit

’s free cooling capacity within the calculation. All calculations

for the FSEER use water with 20% ethylene glycol content. Flow rates are kept constant
for all conditions and are determined by the operation at 7/12°C, 35°C ambient.

Free cooling capacity is included within the units EER when available. DX cooling
capacity is included within the Chillers EER when the Free-cooling available is not
sufficient to satisfy the total cooling demand.

ESEER = A.EER

100%

+ B.EER

75%

+ C.EER

50%

+ D.EER

25%

A, B, C and D are weighting factors 0.05, 0.25, 0.47, 0.23.

Temperature

0°C

10°C

20°C

30°C

Capacity Requirement

0.25

0.5

0.75

1

Percentage of Total Hours

0.23

0.47

0.25

0.05
















All performance data is supplied in accordance with BS EN 14511-1:2013