Chillers

LOGICOOL

Chillers

35

Technical Manual : 6521355 V1.8.0 07/2014

Installation Data

PUMPS

Pump Statement

When installing circulating water pumps or equipment containing them, the following rules
should be applied:

Ensure the system is filled with liquid then vented and the pump primed with water
before running the pump, this is required because the pumped liquid cools the pump
bearings and mechanical seal faces

To avoid cavitation the NPSH (Net Positive Suction Head) incorporating a safety
margin of 0.5m head must be available at the pump inlet during operation

PUMP PACKAGES (OPTIONAL EXTRAS)

Flow Schemes:
A

Standard Unit - No Pump

B

Single Head Pump

C

Run/Standby Pump

1

Filter Ball Valve

8

Differential Pressure Transducer

2

Pump

9

Auto Air Vent

3

Non Return Valve

10 Mixing Valve

4

Water Supply & Return

11 DRV (Flushing Bypass)

5

Drain

12 Binder Points

6

Ball Valve

13 Free Cooling Coil

7

Plate Evaporator

Interlocks & Protection

Always electrically interlock the operation of the chiller with the pump controls for
safety reasons.

CAUTION

Failure to will invalidate the chiller warranty.

CAUTION

Do not rely solely on the BMS to protect the chiller against low flow conditions.

PT

1

A

4

5

6

7

8

12

11

13

9

2

3

10

B

C