Standard recommended installation, Logicool ™ chillers, Installation data – Airedale LogiCool FreeCool 40kW User Manual

Page 34

Advertising
background image

LOGICOOL

Chillers

34

Chillers

Technical Manual : 6521355 V1.8.0 07/2014

Installation Data

STANDARD RECOMMENDED INSTALLATION
(Parts Supplied by Others)

General

Airedale offers a wide range of optional extras to suit various applications including
integral pump, please refer to

Optional Extras - General

, on page 9 for details.

CAUTION

Should non Airedale parts be used, the following installation recommendations
should be adhered to. Failure to do this will invalidate the chiller warranty.


(3)

(2)

(1)

P

P

P

(1) Pressure Sensors
(2) Filter 1 1/16 BSP
(3) Pump

CAUTION

Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty

CAUTION

The correct operation of the flow proving device is critical if the chiller warranty is
to be valid.

CAUTION

Following components are fitted within the chiller unit as standard:

Temperature Sensors

Drain Point

Auto Air Vent

Differential Pressure Monitoring of Evaporator

Pressure Sensing Points

20 Mesh Inlet Filter

Component
Recommended
Requirements

The recommended requirements to allow commissioning to be carried out correctly are:

The inclusion of Binder Points adjacent to the flow and return connections, to allow
temperature and pressure readings

A flow switch or equivalent, fitted adjacent to the water outlet side of the unit Chiller

A water-flow commissioning valve set fitted to the system

In multiple chiller installations, 1 commissioning valve set is required per chiller

Isolating valves should be installed adjacent to all major items of equipment for ease
of maintenance

Balancing valves can be installed if required to aid correct system balancing

All chilled water pipework must be insulated and vapour sealed to
avoid condensation

If several units are installed in parallel adjacent to each other, reverse return should
be applied to avoid unnecessary balancing valves