Chillers

LOGICOOL

Chillers

21

Technical Manual : 6521355 V1.8.0 07/2014

Performance Data

CAPACITY DATA - FREE COOLING

Determine the Free Cooling capacity as follows using the graphs provided:

Example

Model Ref.

= LCC40

Ambient:

= 35°C

Fluid

= 20% Ethylene Glycol

Inlet Fluid Temp.

= 7°C

Outlet Fluid Temp.

= 12°C (5°C

T)

Customer Permanent Head Load

= 20 kW



Calculate Waterflow l/s

Flow =

Output

3.9 x

ΔT

Flow =

33.7

3.9 x 5

Flow =

1.73 l/s


Select Free Cooling Curve

ΔTFC (°C)=

Return Water Temp - Ambient Temp

ΔTFC (°C)=

15 - 5

ΔTFC (°C)=

10°C


Free Cooling (kW)

As plotted on graph =

30kW

Where:
Output = (kW)

Cooling Duty, Output kW, refer to

Capacity Data - DX (Mechanical) Cooling

,

on page 20

ΔT

= (°C)

Difference of Entering Water and Leaving Water temperature

ΔTFC = (°C)

Difference of Leaving Water temperature and Ambient temperature















All performance data is supplied in accordance with BS EN 14511-1:2013