Sound Data

SOUND DATA

Global Chiller Sound Level Values

Sound
Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

LCC20

Power

85

82

86

82

78

80

79

74

Pressure

@ 10m

53

50

54

50

46

48

47

42

LCC40

Power

86

83

86

86

82

81

78

72

Pressure

@ 10m

54

52

55

54

50

49

46

40

1

dB(A) is the overall sound level, measured on the A scale.

2

All sound data measured at nominal conditions: Water in/out 12/7°C at 35°C ambient.

3

Based on standard unit, for units fitted with optional pump packages, please contact Airedale.

The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a
reflective base. If the equipment is placed adjacent to a reflective wall, values may vary to those stated,
typically increasing by 3dB for each side added.