Electrical data, Logicool ™ chillers, General specification – Airedale LogiCool FreeCool 40kW User Manual

Page 30

Advertising
background image

LOGICOOL

Chillers

30

Chillers

Technical Manual : 6521355 V1.8.0 07/2014

General Specification

ELECTRICAL DATA

LCC20

LCC40

Unit Data

Nominal Run Amps

(1)

A

14

28

Maximum Start Amps

(2)

A

103

117

Permanent Supply

VAC

230 V 1 PH 50 Hz

Mains Supply

VAC

400 V 3 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

Rec Mains Fuse Size

A

25

40

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

35 (Direct to Isolator)

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

25

25

External Trace Heating

Available (fitted by others)

W

500

500

AC Condenser Fan - Per Fan

Quantity

1

1

Motor Size

kW

0.98

1.80

Full Load Amps

A

1.75

3.80

Locked Rotor Amps

A

6.20

11.00

Compressor - Per Compressor

Quantity

1

1 + 1

Motor Size

kW

6.8

6.8 / 6 4

Nominal Run Amps

(1)

A

12.1

12.1 / 11.7

Start Amps

(2)

A

101

101 / 101

Type Of Start

Direct on line

OPTIONAL EXTRAS

Compressor Oil Heater Rating

W

70

70 / 70

Electronic Soft-start

Nominal Run Amps

(1)

A

14

28

Maximum Start Amps

A

63

77

Recommended Mains Fuse

A

25

40

EC Condenser Fan - Per Fan

Quantity

1

1

Full Load Amps

A

3.10

4.10

Motor Size

kW

1.85

2.60

Water Pump

Single Head or Run/Standby - Standard

Unit Nominal Run Amps

(1)

A

15

30

Recommended Mains Fuse

A

25

40

Motor Size

kW

0.37

0.50

Full Load Amps

A

1.40

1.90

Single Head or Run/Standby - Larger

Unit Nominal Run Amps

(1)

A

16

31

Recommended Mains Fuse

A

25

40

Motor Size

kW

0.75

0.90

Full Load Amps

A

2.30

3.00

(1)

To ARI standard conditions ARI 540 (7.2°C evaporating; 54.4°C condensing).

(2)

Starting amps refers to the direct on line connections.