PUMP PACKAGES
(OPTIONAL EXTRAS)

Use the formula below and the graphs provided to calculate the External Head Available:

Example:

Model Ref.

= LCC40

Ambient:

= 35°C

Fluid

= 20% Ethylene Glycol

Inlet Fluid

= 7°C

Outlet Fluid

= 12°C (5°C

T)

Pump Selection

= Single Standard

Water Flow l/s

= 1.87 l/s


EHA (kPa) =

External Head Available

EHA (kPa) =

Total Pump Head Available

-

Unit Waterside Pressure Drop

EHA (kPa) =

165 - 82

EHA (kPa) =

83 kPa































All performance data is supplied in accordance with BS EN 14511-1:2013