Chillers

Technical Manual : 6521355 V1.8.0 07/2014

Installation Data

UNIT LIFTING

Employ lifting specialists

Local codes and regulations relating to the lifting of this type of equipment should
be observed

Use the lifting eye bolts/lifting lugs provided

Attach lifting chains to the 4 lifting eye bolts/lifting lugs provided; each chain and eye
bolt must be capable of lifting the whole chiller

Use the appropriate spreader bars/lifting slings with the holes/lugs provided

Chains/slings MUST NOT interfere with the casing of fan assembly to avoid damage

Lift the unit slowly and evenly

If the unit is dropped, it should immediately be checked for damage and reported
to Airedale

CAUTION

Only use lifting points provided.

The unit should be lifted from the top and where possible, with all packing and protection
in position. If any other type of slinging is used, due care should be taken to ensure that
the slings do not crush the casework or coil.





A

A

A =

Minimum lifting chain length of
1500mm